Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: TD-DEV-0123-00109
Parcel: 13701007U

Review Status: Requires Resubmit

Review Details: DEVELOPMENT PACKAGE REVIEW v.1

Permit Number - TD-DEV-0123-00109
Review Name: DEVELOPMENT PACKAGE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/06/2023 CDRC Post Review PENDING ASSIGNMENT
02/15/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The maximum distance between cleanouts in the building sewer shall be 100-feet, measured along the developed pipe length from the upstream entrance of the cleanout. Reference: Section 708.1.1, IPC 2018.
2. The rim elevation of the next upstream sanitary manhole (8051-32, 2513.10’) is higher than the first floor elevation (2510.50’). Provide a backwater valve per Section 714.1, IPC 2018, as amended by the City of Tucson.
02/23/2023 NPPO REQUIRES RESUBMIT See Landscape Comments
02/24/2023 Site Engineering REQUIRES RESUBMIT 1. Include the total area of disturbance on the plans.
2. Include the geotechnical report mentioned in the grading notes in the next submittal.
3. Provide a SWPPP that meets and addresses the minimum requirements/checklist of ADEQ.

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
03/06/2023 Site Landscape REQUIRES RESUBMIT PROJECT: FIRE STATION NO 14
ACTIVITY NO. TD-DEV-0123-00109
ADDRESS/PARCEL: 5580 S NOGALES HY/
ZONING: C-1

This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting.

COMMENTS:
1. Ensure all Zoning and Engineering comments are addressed prior to the Landscape/NPPO comments.
2. Add sight visibility triangles to landscape plans.
3. Is the visitor parking covered by photovoltaic shade canopies like the rest of the staff parking across the site? If not, please add one more tree in the landscaped area adjacent to the parking to meet the parking lot tree requirements.
4. Show curb cuts on the landscape and the commercial rainwater harvesting plan.

If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov or 520-837-4988
02/21/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: PDSD Zoning Review

PROJECT: COT Fire Station #14
Development Package (1st Review)
TD-DEV-0123-00109

TRANSMITTAL DATE: February 21, 2023

DUE DATE: February 24, 2023

COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This plan has been reviewed for compliance with the Unified Development Code (UDC) Administrative Manual (AM) Section 2-06. Also, compliance with applicable development criteria for the proposed use as listed in the City of Tucson Uniform Development Code (UDC) and the UDC Technical Standards Manual (TSM).

Section 3.3.3.G.5.c UDC, an applicant has one year from the date of application to obtain approval of a site plan that complies with zoning and other development requirements in effect at the time of application, unless an ordinance adopted by Mayor and Council during this period states otherwise. A site plan application that has been in review for a period of one year and has not yet been approved is considered denied. To continue the review of a site plan for the property, a new site plan must be submitted that complies with regulations in effect at the time of re-submittal. The new submittal initiates a new one-year review period. One-year Expiration date is January 24, 2024.

CONTENT REQUIREMENTS

1. COMMENT: 2-06.4.3 – Provide the development package case number, TD-DEV-0123-00109, adjacent to the title block on all sheets.

2-06.4.7 - General Notes
The following general notes are required. Additional notes specific to each plan are required where applicable.

2-06.4.7.A - Zoning and Land Use Notes

2. COMMENT: 2-06.4.7.A.1 – The zoning, C-2, listed under Site Data sheet 1, and within the footprint of the buildings on sheets 7-10 is not correct and should be listed as R-2.

3. COMMENT: 2-06.4.7.A.4 – The use specific standards, 4.9.13.F shown under Zoning and Land Use note 16 should be relocated to be included in Site Data Proposed Use.

2-06.4.7.A.8 - For development package documents provide:

4. COMMENT: 2-06.4.7.A.8.b – Revise the lot coverage listed under Zoning and Land Use note 2 to show the building area & vehicle use area.

2-06.4.8 - Existing Site Conditions
The following information shall be provided on the plan/plat drawing to indicate the existing conditions on site and within 50 feet of the site. On sites bounded by a street with a width of 50 feet or greater, the existing conditions across the street will be provided.

5. COMMENT: 2-06.4.8.B – Provide the recordation information for all existing easements shown on the plan.

6. COMMENT: 2-06.4.8.C – Provide dimensioned width of existing paving, curbs, curb cuts, and sidewalks for Nogales Hwy on the plan.

2-06.4.9 - Information on Proposed Development
The following information on the proposed project shall be shown on the drawing or added as notes.

7. COMMENT: 2-06.4.9.A - As it appears some type of land split/reconfiguration is proposed and parcel 137-01-007B exceeds the allowed splits for a property whose boundaries are not fixed by a recorded plat which is divided into four or more lots , tracts, or parcels of land, see UDC Article 11.4.20 definition of a Subdivision, A. A minor subdivision meeting AM 2-07 is required to be submitted and approved prior to approval of this DP.

8. COMMENT: 2-06.4.9.H.2 - Show future sight visibility triangles. On a designated MS&R street, the sight visibility triangles are based on the MS&R cross-section. Show and dimension locations of the future curb & sidewalk on the plan.

9. COMMENT: 2-06.4.9.H.5.d – The bicycle parking space calculation shall provide the number required and provided. Based on the two (2) racks shown on sheet 7 number of short-term provided should be 4.

10. COMMENT: 2-06.4.9.H.5.d – Detail 8 sheet 12 does not addressed UDC Article 7.4.9.B.2.f and the 4’-0” between racks shown on UDC Figure 7.4.9.C.

11. COMMENT: 2-06.4.9.O – The street setback listed under Site Data is not correct. Per UDC Article 6.4.5.C.2 & Table 6.4.5.C-1 the required street perimeter yard setback is 21’ or the (H) Height of the proposed exterior building wall, greater of the two. Based on the height, 28’ FT. shown under Building Data and within the footprint the required street perimeter yard setback is 28’-0”.

12. COMMENT: 2-06.4.9.O – The street perimeter yard setback shown on sheet 7 is not correct. Per UDC Table 6.4.5.C-1 the required setback is measured from the back of future curb. Show the future curb on the plan, see comment 8.

13. COMMENT: 2-06.4.9.O – The side and rear perimeter yard setbacks shown under Site Data and sheet 7 are not correct. Per UDC TABLE 6.3-2.A: DIMENSIONAL STANDARDS FOR THE R-1, R-2, R-3, MH-1, & MH-2 ZONES, R-2 Zone, Nonres Use to Res or Nores Zone the required setback is 10’ or ¾ the Height of the proposed exterior building wall. Based on the height, 28’ FT. shown under Building Data and within the footprint the required side and rear perimeter yard setback is 21’-0”.

14. COMMENT: 2-06.4.9.O – The building height, 28 FT, listed under Building Data and within the footprint of the buildings the proposed building exceeds the allowed 25 FT height, see UDC TABLE 6.3-2.A. Building height is the vertical distance measured from the design grade elevation to the highest point of a flat roof; to the deck line of a mansard roof; or to the middle (between the eave and ridge ) of the highest gable of a pitched or hipped roof. Provide building elevations with the next submittal so that the height can be verified. If the proposed building exceeds 25’ a Board of Adjustment for Variance will be required to exceed the allowed height.


If you have any questions about this transmittal, please contact Nicholas Martell at Nicholas.Martell@tucsonaz.gov.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised development package
01/18/2023 CDRC Application Completeness REVIEW COMPLETED
02/08/2023 CDRC Review Coordinator REVIEW COMPLETED
02/21/2023 Fire New Construction REVIEW COMPLETED
01/19/2023 OK to Submit - Engineering REVIEW COMPLETED
01/19/2023 OK to Submit - Landscape REVIEW COMPLETED
01/25/2023 OK to Submit - Zoning REVIEW COMPLETED
02/24/2023 ROW Engineering Review REVIEW COMPLETED TD-DEV-0123-00109
5580 S. Nogales Hwy

Comments:
1. Any existing curb and sidewalk may remain if it is within tolerance of current standards.
2. New curb returns must have a minimum 25’ radius.
3. Where the sidewalk from the onsite circulation path ties-in to the new concrete sidewalk in the ROW, this needs to be a 5’ X 5’ ADA landing. Please show spot-grades of this landing either on the plan sheet or on the grading plan. A landing must be 60” X 60” and not to exceed 2% cross slope in any direction.
4. A TSMR (Technical Standards Modification Request) is required for the 72’ wide driveway entrance. (Note: maximum curb cut length is 35’.)
5. Protect in place existing streetlights.
6. Protect in place existing catch basins.
7. Protect in place or relocate accordingly, existing regulatory or warning signs.

David Stiffey
DTM Project Coordinator
David.Stiffey@tucsonaz.gov