Review Date Reviewer's Name Type of Review Description Status Comments
N/A Bldg Permits - Post Review Express PENDING ASSIGNMENT
N/A Commercial Electrical PENDING ASSIGNMENT
N/A Outdoor Lighting PENDING ASSIGNMENT
01/16/2025 Commercial Plumbing REQUIRES RESUBMIT 1. Provide plans sealed by an Arizona Registrant. Reference: Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
2. Provide construction documents that are complete and clearly indicate the extent of the proposed work (i.e. remove the “For Information Only” label from the drawings.). Reference: Section 107.2.1, IBC 2018.
3. Revise the site drawing to size of both the water meter and the reduced pressure backflow preventer assembly. Specify the material of construction for the water service pipe Reference: Section 107.2.1, IBC 2018.
4. Provide the total water demand proposed to be served by the new water meter. Reference: Section 107.2.1, IBC 2018.
12/24/2024 PDSD Application Completeness Express REVIEW COMPLETED