Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/09/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The rim elevation of the next upstream sanitary manhole, MH-2 is less than 12” below the first floor elevation of building 1 and the rim elevation of MH-3 is higher than the first floor elevation of building 1. Provide backwater valves for each of the building drains per Section 714.1, IPC 2018, as amended by the City of Tucson.
2. The rim elevation of the next upstream sanitary manholes, MH-7 and MH-8 are less than 12” below the first floor elevation of building 3. Provide backwater valves for each of the building drains per Section 714.1, IPC 2018, as amended by the City of Tucson.