Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.1
Permit Number - TC-UTL-1122-00015
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
01/09/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
01/09/2023 | Commercial Plumbing | REQUIRES RESUBMIT | 1. The rim elevation of the next upstream sanitary manhole, MH-2 is less than 12” below the first floor elevation of building 1 and the rim elevation of MH-3 is higher than the first floor elevation of building 1. Provide backwater valves for each of the building drains per Section 714.1, IPC 2018, as amended by the City of Tucson. 2. The rim elevation of the next upstream sanitary manholes, MH-7 and MH-8 are less than 12” below the first floor elevation of building 3. Provide backwater valves for each of the building drains per Section 714.1, IPC 2018, as amended by the City of Tucson. |
||
12/08/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |