Permit Review Detail
Review Status: Requires Resubmit
Review Details: PRIVATE UTILITY v.2
Permit Number - TC-UTL-0924-00082
Review Name: PRIVATE UTILITY v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/27/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
11/27/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Comment not addressed. Reduced pressure backflow prevention assemblies are required to be installed directly after the water meter for sites that have chemicals, cleaning agents, or other contaminants (e.g. dump stations) that may come in direct contact with water. For installation of reduced pressure backflow assembly instructions, see Tucson Water Standard Detail SD 1802. https://www.tucsonaz.gov/files/sharedassets/public/v/1/living-and-working/parks-and-recreation/documents/sd-1802.pdf Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, https://www.tucsonaz.gov/files/sharedassets/public/city-services/tucson-water/water-quality/documents/backflow-ordinance.pdf [Initial comment: Reduced pressure zone backflow prevention assembly required.] | ||
11/01/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |