Permit Number: TC-UTL-0923-00085
Parcel: 12620001C

Address:
3400 E ZOO CT

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0923-00085
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/26/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
09/26/2023 Commercial Electrical REQUIRES RESUBMIT Please address the electrical plan review comments and provide a written response.

Ref; Utility Plans and Electrical Plans.

1. CA2.1, Area 1. Keyed note #10 makes reference to “ELECTRICAL DUCT BANK”, “REFER TO ELECTRICAL PLANS”. The information or details are not found in the electrical plans. Please clarify.

2. CA2.2, Area 2. Keyed note #10 makes reference to “ELECTRICAL DUCT BANK”, “REFER TO ELECTRICAL PLANS”. The information or details are not found in the electrical plans. Please clarify.

3. CA2.3, Area 3. Keyed note #3 Makes reference to “PVC COMM CONDUITS” and “PULLBOXES”, Keyed note# 10 makes reference to “ELECTRICAL DUCTBANK”, Keyed note #11 makes reference to “ELECTRICAL MANHOLE”, Keyed note #16 makes reference to “NEW COMMUNICATION CONDUITS”, ” PULL BOXES”. All state “REFER TO ELECTRICAL PLANS”. The information or details are not found in the electrical plans. Please clarify.

4. CA2.4, Areas 4, 6. Keyed notes #11 Makes reference to “ELECTRICAL MANHOLE”, Keyed note #12 makes reference to “ELECTRICAL DUCTBANK”. Both notes state “REFER TO ELECTRICAL PLANS”. The information and or details are not found in the electrical plans. Please clarify.

5. CA2.5, Area 5. Keyed notes #3 Makes reference to “ELECTRICAL MANHOLE”, Keyed note #8 makes reference to “ELECTRICAL DUCTBANK”, Keyed note #9 makes reference to “ELECTRICAL TRANSFORMER”. All these keyed notes state to refer to electrical plans. The information or details are not found in the electrical plans. Please clarify.

The Site Lighting is not considered “Private Utilities” and will be reviewed under the building permit.

Ref 2018 IBC section 107.2, 2017 NEC.
09/21/2023 Commercial Plumbing REQUIRES RESUBMIT 1. The frost free hose bibb noted in detail 3/CA4.6 uses a below-grade stop-and-waste valve. This is prohibited unless an approved upstream backflow prevention device is used to protect the upstream potable water source and the downstream outlets are identified with signs that read, “Caution, Nonpotable water, Do Not Drink.” Reference: Sections 608.8 and 608.9.1, IPC 2018.
2. Show how access is to be provided to the backwater valves. Reference: Section 714.3, IPC 2018.
09/21/2023 PDSD Application Completeness REVIEW COMPLETED