Permit Number: TC-UTL-0325-00013
Parcel: 141010130

Review Status: Requires Resubmit

Review Details: PRIVATE UTILITY v.1

Permit Number - TC-UTL-0325-00013
Review Name: PRIVATE UTILITY v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2025 Site Engineering - Standard NOT REQUIRED
04/21/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/17/2025 Commercial Plumbing - Standard REQUIRES RESUBMIT The rim elevation of the next upstream sanitary manhole is more than 12” below the first floor elevation for lots 45, 51, and 84. A backwater valve shall not be installed per Section 714.1, IPC 2018, as amended by the City of Tucson.
03/13/2025 PDSD Application Completeness Express REVIEW COMPLETED