Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-1222-01678
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/12/2023 | Site Zoning | APPROVED | |||
| 01/10/2023 | Site Engineering | NOT REQUIRED | |||
| 01/03/2023 | Site Landscape | NOT REQUIRED | |||
| 01/30/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/30/2023 | Residential Building | REQUIRES RESUBMIT | 1. TEP usually requires the service panel on the property at the closest building to the service transformer. The overhead service conductor over the proposed building requires an 8’ clearance above the roof, E3604.2.1. The necessary mast height at the existing panel location may not be a feasible installation. Update the plans with a relocated service panel and feeder to dwelling or show an overhead line with appropriate clearance over the garage. | ||
| 12/30/2022 | PDSD Application Completeness Express | REVIEW COMPLETED |