Permit Number: TC-RES-1124-06741
Parcel: 117071800

Address:
121 W 17TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.3

Permit Number - TC-RES-1124-06741
Review Name: RESIDENTIAL SOLAR v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/21/2025 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT Permit Review TC-RES-1124-06741 (121 W 17TH ST TUCSON, AZ 85701)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

>>> The following comments were not addressed:

1. Provide a Grounding Electrode System at the detached structures per NEC 690.47.
2. Show the Grounding Conductor’s connection at the modules, mounting and metal support structure.
3. Show grounding details for the mounting equipment and metal support frame, NEC690.43.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
03/24/2025 Residential Building - Standard REQUIRES RESUBMIT Please submit your revised documents and provide a letter with a written response letter addressing each of the comments indicating how the Review comments were resolved. Please note the submittal was incomplete and the plan review was conducted using the information presented. The subsequent review could generate more comments after original comments have been addressed.
*******The following comments were not addressed*****
1. Please submit the complete set of calculations, prepared by an Arizona licensed design professional, used in the design of the Solar Shade Structure. IBC 107.2.1
A. Design required for resistance to gravity and lateral loads
2. Please amend plans to show the following on the plans and in the calculations. IBC 107.2.1
A. 2018 IBC as amended by the City of Tucson
B. Roof Live load and Dead loads
C. Wind speed
D. Design load-bearing values of soils.
E. Risk Category
3. Please amend plans to provide referenced callouts to show all and detail all connections, fasteners, welds bolts, etc., to include the method of connecting the modules to the Solar Shade Structure. IBC 107.2.7
4. Please ensure all sheets used to describe the construction and design of the Solar Shade Structure are sealed by the design professional. Section 107.1, IBC 2018 and Arizona Revised Statutes 32-125, Board of Technical Registration Rules R4-30-304.
Please contact me if you have any questions about these comments.
Mark Masek
Plans Examiner – Building Safety
Planning and Development Services | City of Tucson
main 520.837.4994
email mark.masek@tucsonaz.gov
03/20/2025 Site Zoning - Standard REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Ramiro Olivarez
Planning & Development Services Department – Zoning Review Section

PROJECT:
TC-RES-1124-06741 – Residential Building/Solar Array
121 W 17th St, Tucson, AZ 85701
Plan Review (2nd Review)

TRANSMITTAL DATE: March 20, 2025

This site is zoned O-3 (UDC Section 4.7.15). An detached single-family dwelling is a permitted use in the O-3 zone.
Email the reviewer below directly on resubmittal for faster review.

New Comment 1: Zoning acknowledges that all the signed neighbor waivers requested were provided. However, all signed neighbor waivers must be placed/annotated on the site plan.

New Comment 2: The signed neighbor waivers must indicate the exact distances the structure will be constructed from the property line. (i.e. 6’ 9” feet from the property line as depicted on the site plan.)

**Previous comments will remain until fully addressed:

3. (Previous Comment) In the O-3 zone, setbacks to adjoining properties are 10’ or ¾ the height of the structure’s walls. The proposed setbacks for this structure are 6’ 9” to the west, 6’ 4” to the south, and 6’ 9” to the east.

4. (Previous Comment) Detached structures are permitted to be built to the lot line with neighbor waivers signed by the adjoining property owners. In this case, you would need signed neighbor waivers for the properties at 124th W 18th St, 726 S 7th Av, and 708 S Rubio Av.

Provide this waiver language on the next site plan for each neighbor:

My name is ______ and I am the owner of the property located at ______. I have reviewed the site plan and I have no objection to the structure being located or construct __ feet from the property line as depicted on the site plan.

Signature: ________

Date: _________

5. (Previous Comment) In case neighbor waivers cannot be obtained, then a Design Development Option (DDO) variance would have to be requested and approved for reduced setbacks. Contact Georgia Pennington at georgia.pennington@tucsonaz.gov for more information about the DDO process and an application.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Updated site plan with detailed comment response letter indicating responses to Site Zoning comments above.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
02/23/2025 PDSD Application Completeness Express REVIEW COMPLETED