Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-1124-06608
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit ReviewTC-RES-1124-06608 (2133 E MONTEREY VISTA TUCSON, AZ 85713)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).

1. Provide electrical load calculations for determining the service panel can support the additional electrical load for the new WH, E3602.2.
2. Provide a panel schedule showing wire size and OCPD of each new circuit for the new WH and softener, E3702.2.