Permit Number: TC-RES-1024-06207
Parcel: 123030860

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-1024-06207
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/25/2024 Site Engineering NOT REQUIRED
10/25/2024 Site Landscape NOT REQUIRED
12/05/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/07/2024 Residential Building REQUIRES RESUBMIT TC-RES-1024-06207
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings.

Provide a response letter on separate file with the updated construction plan set.

Each dwelling unit with kitchen requires a separate Pima County assigned street address after Zoning approval, R319. Show Pima County assigned unit numbers at each dwelling on the site plan. https://www.pima.gov/1010/Addressing-Frequently-Asked-Questions

An impact fee payment is required for an ADU at the time of permit payment.

GENERAL COMMENTS :

1. All plans submitted for a newly constructed one- or two-family dwelling after July 1, 2009 require a solar photo-voltaic system, or future installation preparation City of Tucson Ordinance #10549 .
a. Show a minimum 300 SF clear solar-ready zone on a roof or framing plan, T103.3.
b. Label a double breaker space for future Photo Voltaic on the panel schedule opposite end from the main/supply side, T103.9. Provide a future PV breaker space at the last panel space.
2. Show compliance with the Electric Vehicle Supply Equipment Ordinance adopted by the City of Tucson Ordinance #11844 on 6/22/2021. Include a 40 ampere 240-volt dedicated branch circuit with a NEMA 14-50R receptacle for charging an electric vehicle at a proposed parking space.

SITE PLAN:

1. Show the location and size of buildings, utility meters and gas, water, electrical, and sewer, R106.1.1. Each dwelling requires an appropriate source of electrical and water supply. Show the location and size of lines with connection points, R106.1.1. Identify the utility lines requiring upgrade or replacement.

PLANS:

1. Notate a cool (white) roof finish (greater than 60 SRI) as required by the ADU provisions.
2. Show a maximum ½” floor elevation changes at a notated accessible route entrance on the floor plan, R106.1.1. Include all threshold conditions for a route from the exterior into the living space.

SECTIONS - DETAILS:

1. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. Update detail #1 sheet S2.0.
2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38. Clarify the ceiling/roof insulation detail showing the air-impermeable rigid insulation material adhered to either side of the roof sheathing and the batt insulation in contact with the roof material. Update the details on sheet S4.0

PLUMBING PLANS:

1. The Tucson Water Department limits flow rates for the water meter size in compliance with P2903.7. Show an appropriate water meter size for the additional demand.
2. Show each gas pipe segment sized in conformance with Table G2413.4(1). Update the distance from meter entries on the gas demand schedule for consistency with the meter location shown on A1.0 and P1.0.

MECHANICAL PLANS:

1. Provide (an HVAC system with fresh air intake) whole-house mechanical ventilation with controlled exhaust, R303.4; N1103.6 & M1505.4. Show the minimum airflow rate setting and location of the device requiring this adjustable setting. A one-bedroom dwelling under 1501 SF requires a 30 CFM continuous setting.

ELECTRICAL PLANS:

1. TEP may require the service panel for the property at the closest building to the service transformer. A service line change or a new meter location must be coordinated with TEP for approval. Update the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel if TEP does not approve two separate service meters, NEC 225.30 and E3403.
2. Provide the Electric Vehicle Supply Equipment 40 ampere 240-volt dedicated branch circuit with a NEMA 14-50R receptacle and label the circuit “EV Ready” and locate the receptacle at a parking area, N1104.2.1. Include the Electric Vehicle load entry (typically 7680 watts) in the electrical load calculations (continuous demand) like the HVAC entry, N1104.2.2.

OUTDOOR LIGHTING CODE

1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/pdsd
12/05/2024 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Bobby Parsons
Zoning Section Review

PROJECT: TC-RES-1024-06207
2715 E Adams Street Tucson, AZ 85716
ADU (1st Review)

TRANSMITTAL DATE: 12/5/2024

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The site plan should be designed to include the information as noted on the sample site plan. See https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/residential_plot_plan_requirements.pdf for reference.
2. Comment: Per UDC 6.4.3.C, “Roofed areas, open on at least one side, which provide shelter to exterior areas, such as balconies, entrances, stoops, and terraces , provided they are not used for utilities , maintenance, laundry, storage, or motor vehicle parking” are exempt from lot coverage calculations. Please remove the porches from and ramada from your lot coverage calculations and update the total.
3. Please dimension the half right of way to the face of curb and from face of curb to the property line along E. Adams Street.
4. The legal description listed is incorrect. Per https://gis.pima.gov/maps/detail.cfm?&parcel=123030860, the legal description should read New Deal Acres E62.5’ Of S140’ Of L 3 Blk 21. Please update.
5. Comment: Additional comments may be forthcoming depending on responses to zoning comments and revised plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov (520) 837-4977.
10/25/2024 PDSD Application Completeness Express REVIEW COMPLETED