Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2025 NPPO Standard NOT REQUIRED
10/24/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/09/2025 Residential Building REQUIRES RESUBMIT TC-RES-0925-04730
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment updates; revisions are processed if changes occur after the permit is issued.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:

The City of Tucson adopted the 2018 IRC with amendments and building ordinances for all dwellings.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

GENERAL COMMENTS :

1. Remove the delta update symbols added from previous permit comments. Sheets E-1, M-1, S-1 and S-2.

SITE PLAN:

1. Show the correct building square footage, R106.1.1.

PLANS:

1. Identify each wall line needed for enclosing a complete rectangle with sides no greater than 60’, Figure R602.10.1.1. Place these lines no further than 4’ from an actual parallel wall, so that corners are no further than 10’ from a “qualifying” braced wall panel. Show interior braced wall panels with foundation anchor bolt connection to bottom plates, R602.10.8.3 and R403.1.6, and roof connections, R602.10.8.2.

SECTIONS - DETAILS:

1. Provide an interior braced wall section detail with reinforced foundations for anchoring exterior framed walls including ½” anchor bolts with 7” embedment, R403.1.6. Update detail #2 sheet S-2.

MECHANICAL PLANS:

1. Provide demand calculations in accordance with Manual J/D/S standards, M1401.3, M1601.1 as noted at the mechanical specifications schedule.
2. Show a means of make-up air to the laundry closet (transfer grille, louvered or undercut door), M1307.

OUTDOOR LIGHTING CODE

1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.

Please contact the plans reviewer if you have any questions:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
10/03/2025 Residential Engineering REQUIRES RESUBMIT Permit: TC-RES-0925-04730
Location: 1358 N APACHE DR
Review Date: 10/3/2025
Site Engineering Comments:
1. An NPPO will be required as stated by the final plat for Apache Drive Lots 1-3.
2. Per the City of Tucson Inclusive Home Design Ordinance (https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/inclusivehomedesignordinance.pdf), all new dwellings have a requirement to provide an “accessible route from public and common areas, including, but not limited to, a driveway or public street or sidewalk”. Draw, dimension, and label an accessible route from the driveway (or apron), sidewalk, or street to an accessible entrance. Ensure the route meets accessibility standards as articulated in Sections 402-404 of the ADA Accessibility Standards (https://www.access-board.gov/ada/chapter/ch04/). See TSM 7-01.4.3 for specifications, including slope and composition materials.
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
10/08/2025 Residential Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL
FROM: Roxanne Johnston
Planning & Development Services Department – Zoning Review Section
PROJECT: TC-RES-0925-04730
1358 N Apache Dr, Tucson, AZ 85745
New Residential Duplex (1st Review)

TRANSMITTAL DATE: 10/08/2025

This site is located within the R-2 Zone (UDC 4.7.9). A duplex is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, .9, & .10.

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Correct plans, as noted in the comments below, along with a response letter indicating how all Site Zoning comments were addressed.
1. Under the Code Revie block on Sheet C0.0, which references the number of parking spaces required, please provide an additional 3 parking spaces. Per the City of Tucson’s Unified Development Code Article 7, Table 7.4.4-1, the minimum number of parking spaces per unit is 2 spaces per dwelling unit plus a visitor parking space at a ratio of 0.25 per unit.

2. Indicate the name of the owner(s) on the site plan.

For questions regarding Zoning comments, please contact me at: Roxanne.Johnston@tucsonaz.gov.
09/30/2025 PDSD Application Completeness Express REVIEW COMPLETED