Permit Number: TC-RES-0925-04477
Parcel: 123051060

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0925-04477
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/13/2025 Site Zoning - Standard NOT REQUIRED
10/13/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/06/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0925-04477
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

SITE PLAN:

1. Show the location of both existing and proposed electrical panels and the location of the conduit between panels, R106.1.1.

PLANS:

1. Show the meter height above ground in compliance with TEP service entrance standard SR-310. Include the minimum 3’-6” to center of meter requirement.
2. Show the minimum trench depth of 36” at note #4.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
09/12/2025 PDSD Application Completeness Express REVIEW COMPLETED