Review Date Reviewer's Name Type of Review Description Status Comments
10/12/2023 Residential Building APPROVED
10/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/11/2023 Site Engineering REQUIRES RESUBMIT 1. The 15' wide alley can only be used a secondary access but not as primary access, revise to show primary access to N Wilson Av. See UDC 7.4.6.K.2

Stephen Blood
(520) 837-4958
Stephen.blood@tucsonaz.gov
10/07/2023 Site Landscape REQUIRES RESUBMIT This plan has been reviewed for compliance with applicable development criteria in the City of Tucson Unified Development Code (UDC) Administrative Manual (AM) Section 2-11 and Technical Manual (TM) Section for landscape, native plants and water harvesting. 

1. There must be a NPPO or NPPO waiver.  An NPPO is required per UDC 7.7.3-B.   A Native Plant Preservation Plan, Section 7.7.4, is required to be submitted or approved or a request for an exception from the Native Plant Preservation requirements approved in accordance with Sections 7.7.3.D.3 & .4 of the UDC and Admin. Manual Section 2-11.0.0 prior to Grading Plan approval.   The NPPO Waiver must be signed by a licensed Landscape Architect, licensed arborist, or horticulturist with a BS.and submitted with site photos of the existing plants.

If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov
10/13/2023 Site Zoning REQUIRES RESUBMIT FROM: Nick Ross
PDSD Zoning Review Section
PROJECT: TC-RES-0923-08235, 530 N. Wilson Ave.
Zoning: R-1
DATE: ‎10/13/23
COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.
1. Primary access must be provided from a public street. The alley to the north is only 15ft wide and can be used for secondary access only.
2. The required setback for interior property lines in the R-1 zone is 6ft or 2/3H of the proposed wall height. The north façade has a proposed wall height of 22ft which would require a 14.7ft setback. The proposed setback is 6ft. A Design Development Option (DDO) will be required.
3. The south façade has a proposed wall height of 22ft which would require a 14.7ft setback. The proposed setback is 6ft. A DDO will be required.
4. The east façade has a proposed wall height of 22ft which would require a 14.7ft setback. It is unclear if this requirement is being met based on the site plan provided. Please provide an accurate setback dimension to the east property line to confirm. A DDO for this setback may be required.
If you have any questions about this transmittal please contact nicholas.ross@tucsonaz.gov
10/13/2023 Fire New Construction REVIEW COMPLETED
09/25/2023 PDSD Application Completeness Express REVIEW COMPLETED