Permit Number: TC-RES-0824-04918
Parcel: 134261060

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0824-04918
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/25/2024 Site Engineering NOT REQUIRED
09/25/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/11/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0824-04918 (6849 E NEW HAMPSHIRE DR TUCSON, AZ 85710)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Per the manufacturer’s instructions, you cannot mix P series and S series Optimizers in the same string. See item (4) “It is not allowed to mix S-series and P-series Power Optimizers in new installations in the same string”.