Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0823-07343
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/20/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/20/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. 1. Our records shows 1,784 sq ft of living area (your Manual J submittal shows 2,192 sq ft). Was an addition done without a permit? Please clarify. 2. The Extended Rating Table the you submitted is backwards and can't be read. The image also shows a photocopy of two sheets and captured a quarter portion of one sheet and a quarter of the other sheet. Please submit a readable Extended Rating Table that clearly tells us the unit that you have chosen to meet the home's requirement. 3. Please resubmit. |
||
| 02/16/2024 | PDSD Application Completeness Express | REVIEW COMPLETED | This address has a current violation CE-VIO0623-04300. Please submit a complete set of plans and a detailed narrative with your resubmittal that clearly shows how you have addressed all comments from the code violation. Clarify if the structure is detached or attached, the use, dimensions and setbacks. Provide a floor plan labeling all rooms in the structure. Provide a site plan with all existent structures on property. |