Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0823-07223
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
08/10/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
08/10/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0823-07223 (1622 E LESTER ST TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. New gas pipe and gas fired appliance requires the submission of a gas pipeline template, G2401.1, R301.1: https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf See also: https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf 2. Provide a complete gas pipeing template showing the connection from the meter to all gas appliances. Include pipe size, type and length. Provide appliance demands. G2413.4.1, Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Table G2413.4(7) Polyethylene Plastic Pipe). Note: The length is measured from the meter to the furthest attached appliance for all sizing. 3. Minimum burial depth, 12” for metallic pipe, 18” for non-metallic pipe, G2415.12. 4. Yellow tracer wire required for non-metallic pipe, G2415.17.3. 5. Note on the plans if the new gas pack unit will be in the same location as the existing cooler unit. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
08/10/2023 | PDSD Application Completeness | REVIEW COMPLETED |