Permit Number: TC-RES-0625-02830
Parcel: 130102500

Address:
3101 E 29TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.5

Permit Number - TC-RES-0625-02830
Review Name: RESIDENTIAL ADD/ALT v.5
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/03/2025 Residential Zoning APPROVED
11/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/28/2025 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0625-02830 3rd
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Note the 2018 IRC reference on the plans. Update the 2012 notes on sheet A-04.

Provide a response letter addressing each comment with location of change on the plans. Submit separate letter and plan set files.

PLANS:

1. Show the functional name of each existing adjacent room, R106.1.1. Existing bedrooms with removed windows require code compliance for egress, R310. Include any alteration of door or window openings between existing and proposed rooms.
2. Provide a Roof Framing Plan showing the rafters sized for supporting live and dead structural loads (Table R802.4.1(1)). Change the rafter orientation for shortening the span or provide manufactured joist (LPIs) with an appropriate rating for the span.

MECHANICAL PLANS:

1. Show the HVAC system location and size M1401.3, M1601.1 for the bedroom.

ELECTRICAL PLANS:

1. Show the bathroom receptacle with a separate 20 AMP dedicated circuit, E3703.4 & E3901.6.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
----------------------
10/24/2025 PDSD Application Completeness Express REVIEW COMPLETED