Permit Number: TC-RES-0526-02565
Parcel: 138111880

Address:
6113 S DUNTON AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0526-02565
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/22/2026 Residential Zoning APPROVED
05/19/2026 Residential Engineering NOT REQUIRED
05/28/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/28/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0526-02565
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance. This is the appropriate building code for permit applications submitted after January 1, 2026.

Place the current 2024 IRC reference code on sheet A0. Remove outdated code references from sheet #A104 and GN.

Remove the clouding markings from the plans.

Provide a floor plan of the building before renovations for clarification of the location of construction.

The plans require sufficient detail for demonstrating minimum building code compliance for passing all inspections.

Provide a separate response letter addressing each comment with location of change on the plans.

SECTIONS - DETAILS:

1. Provide a wall section detail with 12” x 12” foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
2. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.

MECHANICAL PLANS:

1. Show the furnace location, M1401.3, M1601.1.

ELECTRICAL PLANS:

1. Clarify the location of circuit #19, R106.1.1.
2. Show a smoke alarm in the bedroom and outside the doorway in the immediate vicinity with an electrical circuit, R314.3
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
4. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, E3703.2 and E3901.3.
5. Provide GFCI protection for appliance receptacle outlets, E3902.12. Include:
1. Drinking water coolers
2. High pressure spray washing machines
3. Sump pumps
4. Dishwashers
5. Electric ranges
6. Wall-mounted ovens
7. Counter-mounted cooking units
8. Clothes dryers
9. Microwave ovens