Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0523-05107
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/24/2023 | Site Zoning | APPROVED | |||
| 05/12/2023 | Site Engineering | NOT REQUIRED | |||
| 06/15/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/15/2023 | Residential Building | REQUIRES RESUBMIT | Show the yard water pipe size on the site plan. Minimum 1" required for added demand. The ridge beam is undersized. Consider a glulam 3.5"x9" or 5-1/8"x7-1/2". Show smoke alarms inside and outside of bedroom doors. |
||
| 05/11/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |