Permit Number: TC-RES-0523-05107
Parcel: 138220520

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0523-05107
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/24/2023 Site Zoning APPROVED
05/12/2023 Site Engineering NOT REQUIRED
06/15/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/15/2023 Residential Building REQUIRES RESUBMIT Show the yard water pipe size on the site plan. Minimum 1" required for added demand.

The ridge beam is undersized. Consider a glulam 3.5"x9" or 5-1/8"x7-1/2".

Show smoke alarms inside and outside of bedroom doors.
05/11/2023 PDSD Application Completeness Express REVIEW COMPLETED