Permit Number: TC-RES-0523-04991
Parcel: 11201060A

Address:
2625 E CLAYS AL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0523-04991
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/13/2023 Residential Building REQUIRES RESUBMIT 1. Clarify the placement and amount of ceiling/roof insulation, R806.

2. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38.
06/05/2023 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM: Nathan Herrera
Planner

PROJECT: TC-RES-0523-04991
Address: 2625 E Clays AL. Tucson, AZ. 85716
Parcel: 112-01-060A
Zoning: R-1
Existing Use: Single Family Residence
Project Description: Garage Conversion/Addition

TRANSMITTAL DATE: 6/5/2023

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 - .9.

Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Per UDC Section 6.3-2.A, setbacks in the R-1 zone are the greater of 6’ or 2/3 Height of the proposed exterior building wall.

Provide dimensions for the height of all structures to the elevation drawings on Sheet A-3 to determine if the required setbacks are being met. Add an elevation drawing for the proposed “Open Ramada” with height dimensions.

If the required setbacks are not being met a Design Development Option (DDO) approval is required. The DDO application and requirements may be retrieved from: https://www.tucsonaz.gov/files/pdsd/forms/2019_DDO_for_Setback_and_Height_UDC.pdf. The completed application shall be submitted as a PDF under assigned permit number TC-RES-0523-04991. Contact Mark.Castro@tucsonaz.gov should you have questions regarding the DDO process.


RESUBMITTAL OF THE FOLLOWING IS REQUIRED: revised residential building permit along with a detailed response letter, which states how all Zoning Review Section comments were addressed. To resubmit visit Tucson Development Center at https://tdc-online.tucsonaz.gov/#/home. Instructions for resubmittal - https://www.tucsonaz.gov/files/pdsd/website/Resubmittals.pdf.

If you have any questions about this transmittal, please contact Nathan Herrera at Nathan.Herrera@TucsonAZ.gov or at 520-837-4894.
05/08/2023 PDSD Application Completeness Express REVIEW COMPLETED
05/15/2023 Site Engineering REVIEW COMPLETED
05/15/2023 Site Landscape REVIEW COMPLETED