Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0423-04272
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/02/2023 | Site Zoning | APPROVED | |||
| 04/17/2023 | Site Landscape | NOT REQUIRED | |||
| 05/09/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/09/2023 | Residential Building | REQUIRES RESUBMIT | 1. Show compliance with R310 providing egress from the existing bedroom with minimum net clear opening area of 5 SQ FT. Sheet #2 shows an existing window removal. Verify that this room has another egress window or show the installation of a new egress window. 2. Protection of all interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. 3. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF. Show a R-5 layer of foam board against the roof deck on sheet #5. |
||
| 04/12/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 04/11/2023 | PDSD Application Completeness Express | REVIEW COMPLETED | |||
| 04/20/2023 | Site Engineering | REVIEW COMPLETED |