05/03/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
05/03/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0323-03786 (5250 S CAMPBELL AV Unit:UNIT 123 TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Code reference, 2018 International Residential Code (IRC). 1. Main line from Meter to the first T is undersized for the total demand and developed length. This first segment requires 1” pipe. Longest length is 60’ + 8’ to furnace = 68’, G2413.4.1. Total demand = 135k BTU. See Table G2413.4(1). Note: ¾” is ok after the first T. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||