Permit Number: TC-RES-0323-03786
Parcel: 140160130

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2

Permit Number - TC-RES-0323-03786
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/03/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
05/03/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0323-03786 (5250 S CAMPBELL AV Unit:UNIT 123 TUCSON, AZ 85706)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC).

1. Main line from Meter to the first T is undersized for the total demand and developed length. This first segment requires 1” pipe. Longest length is 60’ + 8’ to furnace = 68’, G2413.4.1. Total demand = 135k BTU. See Table G2413.4(1).
Note: ¾” is ok after the first T.