Permit Number: TC-RES-0323-03447
Parcel: 112032370

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0323-03447
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/30/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/30/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0323-03447 (3325 N FORGEUS AV TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

General Comments:
1. Items built without a permit may require alteration or improvement for code compliance with the 2018 IRC, R105. Show the as-built addition with necessary alterations for achieving code compliance.
2. Any structure placed in the 3-foot fire separation distance from the neighboring property line requires not less than one-hour fire-resistive construction for reducing fire spread across the property line, R302.1. Fire rated materials are found in IBC Table 721.1(2), Items 15-1.1 to 16-1.3.

Roof Framing Plan:
1. 2x4 Rafters are undersized for the expected live and dead loads and given span, Table R802.4.1(2). Provide rafter support sufficient for 20psf live load and 15psf dead load or provide an engineer’s calculation and seal for the structural design.
2. Notate all roof slopes appropriate with selected material, R901.1. (Minimum allowable slope for Built-up roof is ¼” per foot, R905.9.1. Minimum allowable slope for roll roofing is 1” per foot, R905.5.2.).
3. Roof projections extending into the 3-foot fire separation distance to the neighboring property line require not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). The fire protected overhang may not extend closer than 24” from the property line.
4. Eave overhangs shall not exceed 24”, R804.3.2.1.1.

Structural Plan:
5. Provide a complete braced wall design, R602.10, or simplified design, R602.12.

Electrical Plan:
6. Provide a panel schedule showing the main ampacity consistent with the load summary, E3602.1 & E3706.2.
7. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2. This may require a floor mounted receptacle outlet within 18” of the window wall, R3901.2.3.
8. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6. Show bathroom receptacles with ground fault circuit interrupting protection, E3902.
9. Verify the water heater circuit size for serving the load, E3702.11. #10 AWG wire can only serve a max 30A breaker.
10. Use Table E3705.5.3 for sizing 15, 20 & 30 AMP branch circuit conductors and protection ratings.

Plumbing Plan:
11. Show a pressure and temperature relief valve at the water heater. Note a metallic T&P line terminating at the exterior 6 inches above grade facing down, P2803.6.1.
12. Provide a water heater spec sheet for determining the minimum circuit size for safely operating the device at full capacity, P2801. See Circuits 1/3, 5/5, 9.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/17/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0223-03447
3325 N Forgeus Av. - R-1
Detached Accessory Structure (2nd Review)

TRANSMITTAL DATE: Ma7 17, 2023

COMMENT: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. COMMENT: Provide a residential plot plan that meets the requirements found at: https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf, to include but not limited to:
a. This comment was not addressed. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10’, 1” = 20’ etc.
b. This comment was not addressed. Show the 5’ utility easement that runs along the south & west property line on the plot plan.

2. This comment was not addressed. Perimeter yard setbacks have been measured from design grade since the approval of the Land Use Code in 1995. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Based on a wall height of 9’-4” for the wall adjacent to the west property line the required perimeter yard setback from the proposed structure to the west property line is 6’-3”, proposed setback is 6’-0”. The reduced perimeter yard setback can be dealt with in one of two ways: 1) Per UDC Article 6.6.2.D An accessory structure that exceeds the allowable height of a wall within a perimeter yard and is detached from a principal structure shall comply with the perimeter yard width standards of the principal structure, except that the accessory structure may be built to a parcel line with the consent of the adjoining or, when separated by an alley, adjacent property owner(s). To secure this neighbor setback waiver the following statement must be provided on the plot plan and be signed and dated by the adjacent property owner(s):
My Name is____________________ and I am the owner of the property located at _______________________. I have reviewed the site plan and I have no objection to structure being located or constructed________ feet from the property line as depicted on the site plan. Signature: _____________________________
Date: ________________________________
2) Include the perimeter yard setback in the Design Development Option (DDO) required for the wall height as stated below. COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1). 3. The maximum height of a wall or fence within a perimeter yard shall be six (6) feet (UDC Section 6.6.2.I). The maximum height of a retaining wall is ten (10) feet from design grade and no higher than six (6) feet measured from the top of the retaining portion of the wall (UDC Section 6.6.2.I.2). A Design Development Option (DDO) must be submitted and approved for the proposed wall height, DDO application and requirements can be found at: https://www.tucsonaz.gov/files/pdsd/forms/DDO_for_Setback_and_Height_UDC_8.11.20.pdf. If you have questions about the DDO application or process please contact Mark Castro at Mark.Castro@tucsonaz.gov.

3. This comment was not addressed. As the proposed wall is located within the 5’-0” utility easement, provide written approval allowing the wall within the easement from all utilities who have rights to this easement.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/04/2023 PDSD Application Completeness Express REVIEW COMPLETED