Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0126-00263
Parcel: 133440060

Address:
860 N STONER AV

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR REVISION v.1

Permit Number - TC-RES-0126-00263
Review Name: RESIDENTIAL SOLAR REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2026 Residential Zoning APPROVED
04/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/02/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

1) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that the product is UL listed and code compliant E606.5 NEC 230.67
04/02/2026 PDSD Application Completeness Express REVIEW COMPLETED