Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-MDP-1224-01371
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/30/2025 | Commercial Electrical | APPROVED | |||
| 01/30/2025 | Outdoor Lighting | APPROVED | |||
| 01/30/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/30/2025 | Commercial Plumbing | REQUIRES RESUBMIT | 1. Comment not addressed. [Initial comment: Provide a design for the water service to the building, including pipe material, pipe sizes, and valves. Reference: Section 107.2.1, IBC 2018.] 2. Comment not addressed. [Initial comment: Provide a design to show how the building sewer is connected to the private sewer collection system. Show the pipe material, pipe size, cleanouts, and backwater valves. Reference: Section 107.2.1, IBC 2018.] 3. Comment not addressed. [Initial comment: The use of saddle-type fittings to connect to a private sewer is prohibited. Use directional wye fittings to connect the building sewers to the sewer main. Reference: Section 707.1 (6), IPC 2018.] |
||
| 01/30/2025 | Water - PDSD | REQUIRES RESUBMIT | Comment not addressed. [Initial comment: Provide the size of the water meter serving this building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.] | ||
| 01/28/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |