Permit Number: TC-MDP-0924-01053
Parcel: 118122120

Address:
328 E 24TH ST

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-0924-01053
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
10/08/2024 Site Engineering APPROVED
09/26/2024 Fire New Construction NOT REQUIRED
10/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
10/03/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-MDP-0924-01053 (328 E 24TH ST Unit:UNIT 1 TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Provide elevation measurements for Next Upstream Manhole cover and Finished Floor Elevation. Provide Backwater valve protection as required.

Backwater valve protection:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf Section P3008.1 Where required. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor.


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
09/25/2024 ROW Engineering Review REQUIRES RESUBMIT Site plan: Show existing and proposed Right-of-Way features.
Driveway (PAG SD 206) Max. width for residential driveway is 20’
Provide additional documentation for ROW connection point of property, Review locations of existing Meter boxes (East edge of property) and show in relation to proposed driveway ( appear meter falls in the driveway)
10/04/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-0924-01053
328 E 24TH ST. – R-2
Duplex (1st Review)

TRANSMITTAL DATE: October 4, 2024

This site is located in the R-2 zone (UDC 4.7.9). A Duplex is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. The lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, and provide a correct calculation. Per UDC Article 6.4.3.B.3.b Vehicular use areas, measured within the outside edges of any area allocated to vehicle use, whether improved or unimproved are included in the lot coverage.

2. Provide a dimension from the centerline of 24th St to the face of curb and from the face of curb to the north property line. Per Construction plan I-523 found at: https://maps-and-records.tucsonaz.gov/construction-plans/details/I-523, the distance from centerline to face of curb is 19.25’ and from face of curb to the property line is 12’.

3. The sheet index is not correct and should only include the sheet submitted.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
09/24/2024 PDSD Application Completeness Express REVIEW COMPLETED