Permit Number: TC-MDP-0923-01567
Parcel: 13216611C

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL PERMIT - SUBDIVISION v.2

Permit Number - TC-MDP-0923-01567
Review Name: SITE FROM MODEL PERMIT - SUBDIVISION v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
11/13/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-MDP-0923-01567 (4566 S FREMONT AV Unit:UNIT 1 TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

>>> The following comments were not addressed.

1. Provide elevation measurements for Next Upstream Manhole and Finished Floor Elevation. Provide Backwater valve protection as required.
Backwater valve protection:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf Section P3008.1 Where required. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor.
2. Clarify the Overhead Electrical connection. There is no existing overhead TEP conductors on the West side of this property. Clarify if TEP is going to be providing Overhead services along an approved utility easement on the West side of the property. Ensure clearance in compliance with 2017 NEC 230.24

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
11/07/2023 Site Engineering REQUIRES RESUBMIT 1. Indicate on the plans that the finished floor elevation is above the regulatory flood elevation as provided in comments on the floodplain use permit.

Lianne Evans
lianne.evans@tucsonaz.gov
11/09/2023 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0923-01567
4566 S. Fremont Av. - C-1
New Duplex (2nd Review)

TRANSMITTAL DATE: November 9, 2023

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the C-1 zone (UDC 4.7.20). a duplex is a permitted use in this zone (Table 4.8-4).

1. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Per UDC Table 6.3-4 the required perimeter yard setback to the north, south, west property line is 10' or ¾(H), (H) = Height of the proposed exterior building wall, the greater of the two dimensions applies. Based on a wall height of 9’-0” the required perimeter yard setback to the south property line is 10’-0”, proposed setback is 6’-0”. Based on a wall height of 11’-8” the required perimeter yard setback to the west property line is 8’-9”, proposed setback is 6’-0”.

Zoning acknowledges a Design Development Option (DDO) has been applied for. Zoning cannot approve of this permit until the DDO process is complete and approved. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
11/09/2023 Zoning Modifications - DDO REQUIRES RESUBMIT FROM: Georgia Pennington, Planner
DATE: 11/9/23

COMMENTS:

1. Provide a revised "Project Description and Applicant's DDO Request" page, stating the reason for the modification as well as an explanation why the modification would be compatible with the neighborhood.

If you have questions about this transmittal, please email georgia.pennington@tucsonaz.gov
11/03/2023 PDSD Application Completeness Express REVIEW COMPLETED