Permit Number: TC-MDP-0923-01567
Parcel: 13216611C

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL PERMIT - SUBDIVISION v.3

Permit Number - TC-MDP-0923-01567
Review Name: SITE FROM MODEL PERMIT - SUBDIVISION v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/02/2024 Residential Building APPROVED
01/22/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/04/2024 Site Engineering REQUIRES RESUBMIT 1. Indicate on the plans that the finished floor elevation is above the regulatory flood elevation as provided in comments on the floodplain use permit. The FFE must be a foot above the base flood elevation of 2496.86 NAVD88. The FFE must be 2497.86 feet NAVD88 or higher.

Lianne Evans
lianne.evans@tucsonaz.gov
01/02/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0923-01567
4566 S. Fremont Av. - C-1
New Duplex (3rd Review)

TRANSMITTAL DATE: January 2nd, 2024

Provided a detail comment response letter with your submittal that clearly shows how you have addressed all comments with your next submittal.

This site is located in the C-1 zone (UDC 4.7.20). a duplex is a permitted use in this zone (Table 4.8-4).

1. Perimeter yard setbacks are based on a measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Per UDC Table 6.3-4 the required perimeter yard setback to the north, south, west property line is 10' or ¾(H), (H) = Height of the proposed exterior building wall, the greater of the two dimensions applies. Based on a wall height of 9’-0” the required perimeter yard setback to the south property line is 10’-0”, proposed setback is 6’-0”. Based on a wall height of 11’-8” the required perimeter yard setback to the west property line is 10', proposed setback is 6’-0”.

Zoning acknowledges a Design Development Option (DDO) has been applied for. Zoning cannot approve of this permit until the DDO process is complete and approved. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Nathan.Herrera@tucsonaz.gov.
01/22/2024 Zoning Modifications - DDO REQUIRES RESUBMIT The submitted DDO application has been deemed complete by staff. If the DDO is approved, provide a copy of your DDO decision letter in addition to a revised plan set and a comment response letter.

If you have questions about this transmittal, please email me at georgia.pennington@tucsonaz.gov.
12/29/2023 PDSD Application Completeness Express REVIEW COMPLETED