Permit Number: TC-MDP-0825-00443
Parcel: 11515530B

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-0825-00443
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/02/2025 Residential Building APPROVED
08/19/2025 Fire New Construction NOT REQUIRED
09/05/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/02/2025 Site Engineering REQUIRES RESUBMIT TC-MDP-0825-00443
714 W CALLE ADELANTO

Site engineering comments are as follows:

1. Neither of the individual site plans for these two developments, TC-MDP-0825-00443 and TC-MDP-0825-00442, include a depiction of the common walk that runs between the Parking areas. If this walk is to be installed, it will need to be elevated to provide vertical separation from the PAAL [TSM 7-01.4.2]. It will also need to be located entirely on the eastern property, MDP-0825-00442, i.e. the parcel line cannot divide the walk.
2. Dimension the Parking area.
3. Include a North Arrow on the full site plan.

Ryan Insalaco
Engineering Associate
ryan.insalaco@tucsonaz.gov
Phone: (520) 837-5351
09/05/2025 Site Zoning REQUIRES RESUBMIT PDSD TRANSMITTAL

FROM:
Bobby Parsons
Zoning Section Review

PROJECT:
TC-MDP-0825-00443
714 W. Calle Adelanto Tucson, AZ 85705
Duplex SFR & ADU (1st Review)

TRANSMITTAL DATE: 9/5/2025

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6,.9, .10.

Comments: Please resubmit revised drawings along with a detailed response letter which states how all Zoning Review Section comments were addressed.

1. Comment: The “full” site plan provided does not match the site plan provided for TC-MDP-0825-00443. The full site plan shows an accessible route between the parking spaces however the site plan provided for TC-MDP-0825-00443 shows the parking spaces located on the property line. Please clarify the discrepancy.
2. Comment: Additional comments may be forthcoming depending on responses to zoning review comments and plans submitted.

If you have any questions about this transmittal, please contact Bobby Parsons at Robert.Parsons@tucsonaz.gov.
08/18/2025 PDSD Application Completeness Express REVIEW COMPLETED
09/05/2025 ROW Engineering Review REVIEW COMPLETED Pedestrian access easement required for shared accessible route
12' Min. between driveways.