Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-MDP-0824-00893
Parcel: 116180040

Address:
919 W FRESNO ST

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.3

Permit Number - TC-MDP-0824-00893
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
09/23/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
09/23/2025 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-0824-00893
919 W FRESNO ST. – R-2
New SFR (3rd Review)

TRANSMITTAL DATE: September 23, 2025

COMMENTS: Provide a detailed response letter with your submittal that clearly shows how you have addressed all Zoning comments.

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

** Previous Zoning Design Development Option comments will remain until the DDOs have been processed.

2. Per UDC Article 6.4.5.C.1.a For single-family and duplex development, the minimum required front street perimeter yard is 20 feet measured from the street property line. Proposed front street perimeter yard setback is 17’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback.

3. Per UDC Table 6.3-2.A the minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As dimensions f rom design grade where not provided on the model plan Zoning has added 6” to the 15’ shown for the south wall height. Based on a 15’-6” wall height the required perimeter yard setback from the proposed SFR to the south property line is 10’-4”, proposed setback is 6’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback.

4. Per UDC Table 6.3-2.A the minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. As dimensions f rom design grade where not provided on the model plan Zoning has added 6” to the 9’ shown for the east wall height. Based on a 9’-6” wall height the required perimeter yard setback from the proposed SFR to the east property line is 6’-4”, proposed setback is 6’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback.

DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Georgia Pennington at Georgia.Pennington@tucsonaz.gov”.

Zoning acknowledges that a DDO application was submitted but it does not appear that it was submitted correctly. Contact Georgia Pennington to ensure that the DDO is submitted correctly.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov.
09/05/2025 PDSD Application Completeness Express REVIEW COMPLETED