Permit Number: TC-MDP-0724-00837
Parcel: 126061170

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-0724-00837
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/01/2024 Fire New Construction NOT REQUIRED
08/20/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/16/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-MDP-0724-00837 (926 N MONTEZUMA AV TUCSON, AZ 85711)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

Demolition:
1. Prerequisite to Approvals: IBC Amendment Section 3303.1.1: At least fifteen (15) days prior to the start of demolition, the applicant shall provide notice to the adjacent property owners of the proposed demolition. Confirmation of the notice may be submitted with the application. Return a completed copy of https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/demolition_confirmation_statement2-14-14.pdf.

Electrical:
2. Provide a grounding electrode on the Riser Diagram for the sub-panel, E3607.3.

Plumbing:
3. Show cleanouts at 100’ intervals and at change of direction exceeding 45 degrees, P3005.2.
4. Protect a cleanout plug from the loads of vehicular traffic. Cleanout assemblies in accordance with ASME A112.36.2M Shall be installed, P3005.2.10.2.

5. Tucson Water Department limits flow rates for each water meter size in compliance with P2903.7. Show an appropriate existing or proposed water meter size.
6. Provide the water pipe diameter between the meter and both shut off valves in compliance with P2903.7. A minimum 1” service pipe is required for supplying water to more than 9.5 fixture units. Show the size of the existing main water line.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
08/15/2024 Site Engineering REQUIRES RESUBMIT This project is in a local regulated floodplain (Alvernon Wash). A floodplain use permit with elevation certificate is required. Based on available data, the base flood elevation where the ADU is proposed is 2491.81 feet NAVD88. The minimum finished floor elevation (FFE) is 2492.81 feet NAVD88. The current proposed FFE on the plans does not meet this requirement. Please revise the plans to state a FFE that meets this requirement and upload the plans to both this permit as well as the floodplain use permit. The floodplain use permit will need to be approved before Site Engineering can approve this building permit.

Mike Ortiz
michael.ortiz@tucsonaz.gov
08/14/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-0724-00837
926 N MONTEZUMA AV. – R-1
New ADU (1st Review)

TRANSMITTAL DATE: August 14, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence with an accessory dwelling unit (ADU) is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.6, 8, & 9 and 6.6.3.

1. The lot coverage calculation is not correct. Review UDC Article 6.4.3 and the example shown on the Residential Plot Plan Requirements found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Building-Safety/Plan-Examples/Plot-Plan-Example, and provide a correct lot coverage calculation. Lot coverage has nothing to do with graded area.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
07/31/2024 PDSD Application Completeness Express REVIEW COMPLETED
08/20/2024 ROW Engineering Review REVIEW COMPLETED No impact to ROW