Permit Number: TC-MDP-0324-00311
Parcel: 120074400

Review Status: Requires Resubmit

Review Details: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1

Permit Number - TC-MDP-0324-00311
Review Name: SITE FROM MODEL TEMPLATE - INFILL BUILDERS v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/02/2024 Site Engineering APPROVED
03/27/2024 Fire New Construction NOT REQUIRED
04/04/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/26/2024 Residential Building REQUIRES RESUBMIT Permit Review TC-MDP-0324-00311 (150 W AVIATION DR TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Provide elevation measurements for Next Upstream Manhole and Finished Floor Elevation.
2. Provide Backwater valve protection as/if required.
Backwater valve protection:
https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf Section P3008.1 Where required. Where the finish floor elevation is less than 12 inches above the elevation of the next upstream manhole cover in the sewer, a backwater valve shall be installed in the building drain or branch of the building drain serving that floor.

3. Show the building sewer line connected to the HCS in compliance with P3005.4. The size of the drainage piping shall not be reduced in size in the direction of flow. (4” S connected to 3” HCS).

4. Tucson Water Department limits 5/8" water meters to a maximum of 11 IRC fixture units or 15 gallons per minute, P2903.7. Show a water meter sized to meet the demand of both dwellings.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
04/03/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-MDP-0324-00311
150 W AVIATION DR. – R-2
New SFR (1st Review)

TRANSMITTAL DATE: April 3, 2024

This site is located in the R-2 zone (UDC 4.7.9). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.6, .9, & .10.

1. Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall UDC Article 6.4.5.B & Figure 6.4.5-A. Where the wall meets the eave of the roof. Based on a 9’-6” wall height the required perimeter yard setback from the propose SFR to the east property line is 6’-4”, proposed setback is 6’-0”. A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
03/20/2024 PDSD Application Completeness Express REVIEW COMPLETED The address on the site plan does not show in our system. Our system shows address "150 W AVIATION DR" while the site plan uploaded shows "150 W AVIATION RD". Please correct Site plan address or see Pima County Addressing to correct this issue.
04/04/2024 ROW Engineering Review REVIEW COMPLETED TC-MPD-0324-00311
150 W. Aviation Dr.

Comments:
1. Driveway apron to be constructed per P.A.G. standard 206.
2. A Right of Way Permit needs to be obtained to connect sewer and water in the ROW.