Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEMOLITION v.1
Permit Number - TC-DMO-0924-00212
Review Name: DEMOLITION v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
10/02/2024 | Commercial Building | APPROVED | Demo only | ||
10/01/2024 | Commercial Mechanical | APPROVED | |||
10/01/2024 | Commercial Plumbing | APPROVED | |||
10/03/2024 | Site Zoning | APPROVED | |||
10/07/2024 | Site Engineering | NOT REQUIRED | |||
10/07/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
10/03/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical plan review comments and provide a written response. 1 Please provide direction or prescribed method for capping off safely, the discontinued branch circuit and feeders after the removal of electrical equipment on the electrical plans per NEC and OSHA standards. Ref; 2018 IBC section 107.2.1, 2017 NEC 90.1(A)(B)(C). |
||
09/25/2024 | Fire New Construction | REVIEW COMPLETED | |||
09/25/2024 | PDSD Application Completeness | REVIEW COMPLETED |