Permit Review Detail
Review Status: Requires Resubmit
Review Details: DEMOLITION v.1
Permit Number - TC-DMO-0124-00017
Review Name: DEMOLITION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/09/2024 | Commercial Building | APPROVED | |||
| 02/08/2024 | Commercial Mechanical | APPROVED | |||
| 02/08/2024 | Commercial Plumbing | APPROVED | |||
| 01/31/2024 | Site Zoning | APPROVED | |||
| 02/08/2024 | Site Engineering | NOT REQUIRED | |||
| 02/09/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/08/2024 | Commercial Electrical | REQUIRES RESUBMIT | Please address the electrical power and lighting in detail on the plans. Also, per Plan Sheet, ‘D1.0, the Demolition Floor Plan Keynotes #21 state to relocate existing electrical panels, “SEE ELECTRICAL DRAWINGS”. Could not locate drawings that address the relocation of the panels. Ref; 2018 IBC section 107.2.1, 2017 NEC, City of Tucson Commercial Plan Submittal requirements. |
||
| 01/31/2024 | Fire New Construction | REVIEW COMPLETED | |||
| 01/31/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |