Permit Number: TC-COM-1225-02357
Parcel: 10602043D

Address:
3960 N STONE AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02357
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/27/2026 Site Zoning Standard APPROVED Interior TI; Reference TZ-CMP-0923-00186
01/27/2026 Water - PDSD Standard APPROVED
01/15/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
01/09/2026 Site Engineering Standard NOT REQUIRED
01/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/23/2026 Commercial Building Standard REQUIRES RESUBMIT January 23, 2026
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Road
Tucson, Arizona 85710

Re: TEEN CHALLENGE THRIFT STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1225-02357
Stantec Project Number: 185215066
Stantec File Number: TUC-26-001

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 9,223 112 No No
Separate Permits: None.
Deferred Submittals: Structural support of overhead coiling door.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the cup dispenser at the point of use water cooler is permanently mounted with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy No. 2008-21]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. The point of use water cooler must be connected to a permanent supply of potable water. Please provide an updated plumbing plan indicating the supply line plumbed to the water cooler. [Ref. City of Tucson Policy No. 2008-21]

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for the updated interior lighting. [Ref. IECC 2018 Sec. C405.3]

Sheet E101

1. Please provide updated load calculations and panel schedules for the new electrical design. [Ref. NEC 2017 Art. 220 & 408.4(A)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/23/2026 Commercial Electrical Standard REQUIRES RESUBMIT January 23, 2026
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Road
Tucson, Arizona 85710

Re: TEEN CHALLENGE THRIFT STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1225-02357
Stantec Project Number: 185215066
Stantec File Number: TUC-26-001

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 9,223 112 No No
Separate Permits: None.
Deferred Submittals: Structural support of overhead coiling door.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the cup dispenser at the point of use water cooler is permanently mounted with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy No. 2008-21]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. The point of use water cooler must be connected to a permanent supply of potable water. Please provide an updated plumbing plan indicating the supply line plumbed to the water cooler. [Ref. City of Tucson Policy No. 2008-21]

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for the updated interior lighting. [Ref. IECC 2018 Sec. C405.3]

Sheet E101

1. Please provide updated load calculations and panel schedules for the new electrical design. [Ref. NEC 2017 Art. 220 & 408.4(A)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/23/2026 Commercial Mechanical Standard REQUIRES RESUBMIT January 23, 2026
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Road
Tucson, Arizona 85710

Re: TEEN CHALLENGE THRIFT STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1225-02357
Stantec Project Number: 185215066
Stantec File Number: TUC-26-001

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 9,223 112 No No
Separate Permits: None.
Deferred Submittals: Structural support of overhead coiling door.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the cup dispenser at the point of use water cooler is permanently mounted with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy No. 2008-21]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. The point of use water cooler must be connected to a permanent supply of potable water. Please provide an updated plumbing plan indicating the supply line plumbed to the water cooler. [Ref. City of Tucson Policy No. 2008-21]

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for the updated interior lighting. [Ref. IECC 2018 Sec. C405.3]

Sheet E101

1. Please provide updated load calculations and panel schedules for the new electrical design. [Ref. NEC 2017 Art. 220 & 408.4(A)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/23/2026 Commercial Plumbing Standard REQUIRES RESUBMIT January 23, 2026
1st Review

Light+Path Architecture LLC.
Attn: Brian G. Hagedon
475 S. Gollob Road
Tucson, Arizona 85710

Re: TEEN CHALLENGE THRIFT STORE
TENANT IMPROVEMENT

City of Tucson Permit Number: TC-COM-1225-02357
Stantec Project Number: 185215066
Stantec File Number: TUC-26-001

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. PLEASE send all response to comments back to the City through the permit portal! Responses sent directly to Stantec will be ignored. Also, please submit complete copies of all permit documents (i.e. plans, calculations, reports, etc.) even if they have not been changed. Please cloud and delta all changes and provide a letter with a written response to each of the comments indicating the action taken.

The scope of this review covers the architectural, structural, plumbing, mechanical, and electrical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
M V-B 9,223 112 No No
Separate Permits: None.
Deferred Submittals: Structural support of overhead coiling door.
Special Inspections: None.

ARCHITECTURAL COMMENTS

General

1. Please indicate that the cup dispenser at the point of use water cooler is permanently mounted with the dispensing end between 34” and 48” above finished floor. [Ref. City of Tucson Policy No. 2008-21]

STRUCTURAL COMMENTS

There are no comments.

MECHANICAL COMMENTS

There are no comments.

PLUMBING COMMENTS

General

1. The point of use water cooler must be connected to a permanent supply of potable water. Please provide an updated plumbing plan indicating the supply line plumbed to the water cooler. [Ref. City of Tucson Policy No. 2008-21]

ELECTRICAL COMMENTS

General

1. Please provide an energy conservation compliance certificate for the updated interior lighting. [Ref. IECC 2018 Sec. C405.3]

Sheet E101

1. Please provide updated load calculations and panel schedules for the new electrical design. [Ref. NEC 2017 Art. 220 & 408.4(A)]


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies,
Senior Plan Reviewer
602-338-9922
trevor.bies@stantec.com
01/26/2026 Fire New Construction Standard REVIEW COMPLETED
01/05/2026 PDSD Application Completeness Express REVIEW COMPLETED