Permit Number: TC-COM-1225-02340
Parcel: 11918034B

Address:
3500 S 12TH AV

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1225-02340
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2026 Commercial Building Standard APPROVED
02/24/2026 Commercial Electrical Standard APPROVED
02/24/2026 Outdoor Lighting Standard APPROVED Approved with comment:
An Outdoor Lighting Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit.

https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-development-services/documents/special_inspection_certificate_odl.pdf
03/11/2026 Site Zoning Standard NOT REQUIRED Per communication w/ Nick Ross and Loran Shamis, public schools are exempt from Site Zoning review.
03/17/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
03/11/2026 Commercial Mechanical Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02340
ADDRESS/PARCEL: 3500 S 12TH AV TUCSON, AZ 85713

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Our local amendment requires that duct smoke detectors be installed in the return duct of air distribution systems moving more than 2,000 CFM. Per Section 202 of the 2018 IMC, an air distribution system is defined as any system of ducts, plenums, and air-handling equipment that circulates air within a space or spaces and includes systems made up of one or more air-handling units. In this case, the air distribution system consists of both 2000 cfm units since both are circulating the air throughout the study room.

Additionally, Section 606.2.2 of the 2018 IMC states that where multiple air-handling systems share common supply or return air ducts or plenums with a combined design capacity greater than 2,000 CFM, the return air system shall be provided with smoke detectors in accordance with Section 606.2.1. Because the study room is being used as part of the return air path (functioning as a return plenum/duct), it is considered part of the air distribution system. Therefore, smoke detectors are required.
03/11/2026 Commercial Plumbing Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02340
ADDRESS/PARCEL: 3500 S 12TH AV TUCSON, AZ 85713

Submit your revised drawings along with a detailed response letter, which states how all comments were addressed. Review will not proceed without the response letter. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review.

If you have any questions about these review comments, I can be reached at Sean.Severson@tucsonaz.gov

COMMENTS:

1. Section 1106.5 states scupper openings shall have a width that is equal to or greater than the circumference of a roof drain size for the same roof area. Based on the flow rate (51 gpm) shown on Sheet A4.0, a 3-inch roof drain would be required per Table 1106.2, which has an approximate circumference of 9.5 inches. Therefore, the scuppers should have a width of at least 9.5”. Reference: Section 1105.2, 2018 IPC
2. Overflow scuppers are missing from the east elevation view on Sheet A5.1. Also, show the secondary overflow system for the portion of the roof draining to the gutter, since the gutter appears to discharge to an interior drain. Reference: section 1108, IPC 2018
02/26/2026 Site Engineering Standard REQUIRES RESUBMIT Permit Activity Number: TC-COM-1225-02340 (1st Review)
Project: New ground up tennis center for Pueblo High School
Location: 3500 S 12TH AV
Review Date: 2/26/2026
Reviewer: Marco Contreras – Engineering Associate - Site Engineering

Site Engineering Comments:
1. Site Engineering has reviewed the plan set provided to ensure compliance with the associated development package and is unable to approve permit TC-COM-1225-02340 until the associated Development Package TD-DEV-0226-00035 is reviewed and approved by all reviewers.

If you have any questions or concerns, please contact Marco Contreras at Marco.contreras@tucsonaz.gov
02/19/2026 PDSD Application Completeness Express REVIEW COMPLETED