Permit Number: TC-COM-1225-02275
Parcel: 14036017D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02275
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/09/2026 Commercial Building Standard APPROVED
01/02/2026 Commercial Electrical Standard APPROVED
01/12/2026 Commercial Plumbing Standard APPROVED
01/12/2026 Site Zoning Standard APPROVED
01/12/2026 Water - PDSD Standard APPROVED
12/23/2025 Site Engineering Standard NOT REQUIRED
01/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/12/2026 Commercial Mechanical Standard REQUIRES RESUBMIT The mechanical plan, M102, shows four high velocity diffusers located in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018.
01/12/2026 Fire New Construction Standard REVIEW COMPLETED
12/19/2025 PDSD Application Completeness Express REVIEW COMPLETED