Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1225-02275
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/09/2026 | Commercial Building Standard | APPROVED | |||
| 01/02/2026 | Commercial Electrical Standard | APPROVED | |||
| 01/12/2026 | Commercial Plumbing Standard | APPROVED | |||
| 01/12/2026 | Site Zoning Standard | APPROVED | |||
| 01/12/2026 | Water - PDSD Standard | APPROVED | |||
| 12/23/2025 | Site Engineering Standard | NOT REQUIRED | |||
| 01/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 01/12/2026 | Commercial Mechanical Standard | REQUIRES RESUBMIT | The mechanical plan, M102, shows four high velocity diffusers located in close proximity to the face of the Type I hood. Verify that the location and type of air outlets complies with the hood manufacturer’s installation instructions and does not reduce the effectiveness of the exhaust system. Reference: Sections 304.1 and 508.1, IMC 2018. | ||
| 01/12/2026 | Fire New Construction Standard | REVIEW COMPLETED | |||
| 12/19/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |