Permit Number: TC-COM-1225-02249
Parcel: 130030150

Address:
2500 E 22ND ST

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1225-02249
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
12/30/2025 Commercial Electrical Standard APPROVED
12/30/2025 Commercial Mechanical Standard APPROVED
01/08/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
12/30/2025 Commercial Building Standard REQUIRES RESUBMIT 1. Sheet 0.1, 2018 IBC 506.3.1 Minimum percentage of perimeter. To qualify for an area factor increase based on frontage, a building shall have not less than 25 percent of its perimeter on a public way or open space. Such open space shall be either on the same lot or dedicated for public use and shall be accessed from a street or approved fire lane. The Site Plan provided and information does not demonstrate a 25% minimum perimeter. DMA
2. Sheet 0.2, 2018 IBC [A]107.2.3 Means of egress. The construction documents shall show in sufficient detail the location, construction, size and character of all portions of the means of egress including the path of the exit discharge to the public way in compliance with the provisions of this code. In other than occupancies in Groups R-2, R-3, and I-1, the construction documents shall designate the number of occupants to be accommodated on every floor, and in all rooms and spaces. Plans do not detail the required means of egress information as listed within this section. DMA
3. Sheet A1.0, 2018 IBC 1106.1 Required. Where parking is provided, accessible parking spaces shall be provided in compliance with Table 1106.1, except as required by Sections 1106.2 through 1106.4. Where more than one parking facility is provided on a site, the number of parking spaces required to be accessible shall be calculated separately for each parking facility. Minimum of 3 spaces is required. DMA
4. Sheet S1.1; Provide complete structural details and structural calculations that detail the scope of work. Also include elevations. DMA
12/30/2025 Commercial Plumbing Standard REQUIRES RESUBMIT 1. Sheet 0.1, 2018 IBC [P] 2902.1 Minimum number of fixtures. Plumbing fixtures shall be provided in the minimum number as shown in Table 2902.1 based on the actual use of the building or space. Uses not shown in Table 2902.1 shall be considered individually by the code official. The number of occupants shall be determined by this code. DMA
01/07/2026 Fire New Construction Standard REQUIRES RESUBMIT Resolve building review comments.
Questions: patricia.shelton@tucsonaz.gov
12/31/2025 Outdoor Lighting Standard REQUIRES RESUBMIT Outdoor Lighting Review TC-COM-1225-02249 (2500 E 22ND ST TUCSON, AZ 85713)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC).
Outdoor Lighting Review:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf

1. The replacement, relocation and installation of new lighting fixtures requires compliance with the City of Tucson Outdoor Lighting Code.
2. Verify the expected use of the new lighting fixture EM3. Is this light only come on in an emergency? Or is it used for normal illumination as well? If this light fixture is used for normal illumination, then it will need to meet the requirements of the Outdoor Lighting Code for color temperature and lumen count.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/18/2025 Site Engineering Standard REQUIRES RESUBMIT Permit: TC-COM-1225-02249
Location: 2500 E 22ND ST
Review Date: 12/18/2025
Site Engineering Comments:
1. The proposed new trash enclosure addition to the existing site will require the submission of a Development Package Site plan UDC 7.4.3.E as this constitutes as site work. In accordance with Unified Development Code (UDC) Article 3.3.3.G.2.c, a site plan (Development Package Permit) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf.
2. Site Engineering is unable to review and approve permit TC-COM-1225-02249 until the associated Development Package is reviewed and approved by all reviewers.
3. For formatting requirements for the development package submission, refer to Administrative Manual 2-06.0.0 Sections 3.0 – 4.9
If you have any questions or concerns, please contact
Marco Contreras
Marco.contreras@tucsonaz.gov
01/08/2026 Site Zoning Standard REQUIRES RESUBMIT FROM: Ramiro Olivarez
PDSD Zoning Review Section

PROJECT: TC-COM-1225-02249
2500 E 22ND ST – C-1
Tenant improvement of an existing bank and exterior improvements (1st Review)

TRANSMITTAL DATE: January 08, 2026

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1. Comment: Per UDC Article 3.3.3.G.2.c, a site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A Development Package (DP) meeting the requirements of the Checklist for Minor Changes to Commercial/Industrial Sites is required to be submitted and approved. The DP is a separate submittal from the building plans. The checklist can be found at:
https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/minor_changes_to_commercial_industrial_sites_.pdf. Site zoning is unable to approve this building permit until the DP has been approved by all reviewers.
2. Comment: Additional comments may be forthcoming based on the use and applicable use specific standards.

If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov
01/08/2026 Water - PDSD Standard REQUIRES RESUBMIT ACTIVITY NO. TC-COM-1225-02249
ADDRESS/PARCEL: (2500 E 22ND ST TUCSON, AZ 85713)
COMMENTS:
1. Please show the size of the water meter serving the building, the size of the backflow preventer associated with the water meter, and the total water demand served by the water meter. Reference: Section 107.2.1, IBC 2018.
12/17/2025 PDSD Application Completeness Express REVIEW COMPLETED