Permit Number: TC-COM-1225-02177
Parcel: 10513032D

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1225-02177
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
01/21/2026 Commercial Building Standard NOT REQUIRED
01/20/2026 Commercial Mechanical Standard NOT REQUIRED No mechanical/plumbing work
01/20/2026 Commercial Plumbing Standard NOT REQUIRED No mechanical/plumbing work
01/21/2026 Fire New Construction Standard NOT REQUIRED
01/06/2026 Outdoor Lighting Standard NOT REQUIRED No modifications to the outdoor lighting.
12/30/2025 Site Engineering Standard NOT REQUIRED
01/15/2026 Site Zoning Standard NOT REQUIRED
01/20/2026 Water - PDSD Standard NOT REQUIRED No mechanical/plumbing work
01/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
01/06/2026 Commercial Electrical Standard REQUIRES RESUBMIT Commercial Electrical Review TC-COM-1225-02177 (4011 N 1ST AV Unit:BLDG J TUCSON, AZ 85719)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).

1. The removal of the GFCI receptacle in the kitchen requires a basic electrical kitchen plan to show code compliance.
2. Show two or more 2O AMP small appliance circuits at the kitchen countertop receptacle outlets; they may also serve the breakfast room and dining room, but not other locations, [NEC 210.52(C)(1)] and [NEC 210.52(B)(1)]. GFCI protected, [NEC 210.8(A)].
3. Show receptacle outlets at each kitchen counter space wider than 12” with no point along the wall line more than 24” from a receptacle outlet, NEC 210.52(C)(1).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
12/30/2025 PDSD Application Completeness Express REVIEW COMPLETED