Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.3

Permit Number - TC-COM-1224-02395
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/14/2025 Site Engineering APPROVED
04/14/2025 Site Zoning APPROVED
04/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/14/2025 Commercial Mechanical REQUIRES RESUBMIT The listing information for the direct venting of the pizza oven calls for the use of a “manufactured chimney.” Specify the construction of the exhaust duct, e.g listed per UL 103 and specifically listed for operation with a positive vent pressure. Reference: Section 503.5.1, IFGC 2018. [Second comment: Provide information regarding the horizontal exhaust duct (e.g. slope, air velocity, etc.).] [Initial comment: The venting of the pizza oven is, “…factory approved for the direct method with a manufactured chimney…” if this is the intent, provide the specification and listing information for the exhaust ducting and show that the horizontal routing and termination complies with the listing. Reference: Section 503.5.1, IFGC 2018.]
04/08/2025 Historic REVIEW COMPLETED Full historic review on the restaurant component of the project by PRS conducted and recommended approval. PDSD Director's Decision Notice pending. Once finalized, applicant may proceed to permitting. No further HPZ review required.
If you have any questions, contact Michael.Taku@tucsonaz.gov
03/24/2025 PDSD Application Completeness Express REVIEW COMPLETED