Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1224-02387
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/11/2025 | Commercial Electrical | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 1/27/2025 5:54:53 PM |
||
02/11/2025 | Outdoor Lighting | APPROVED | Electrical(E) Reviewer Ron Ross rross@safebuilt.com Approved with Comments Reason: Date Completed : 1/27/2025 5:54:53 PM |
||
02/12/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
02/11/2025 | Commercial Building | REQUIRES RESUBMIT | Structural(S) Reviewer Madeline Nelson mnelson@safebuilt.com Approved Reason: Date Completed : 2/10/2025 6:19:36 PM Building(B) Reviewer Andrew Bevis abevis@safebuilt.com Denied Reason: Date Completed : 1/27/2025 12:50:36 PM 17. NEW COMMENT: Sheet A1.5/Door ratings: After reviewing the provided door schedules. It only appears that unit doors have been provided on the door schedule. Many doors have been left off the door schedules, including doors that are required to be rated. Provide properly rated doors in accordance with Table 716.1(2). |
||
02/11/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Mechanical(M) Reviewer Jorge Valido jvalido@safebuilt.com Denied Reason: Date Completed : 2/7/2025 1:40:11 PM 4. (UNRESOLVED) - General - Show all routing of refrigerant piping. (if applicable) Provide shaft details for refrigerant piping. If refrigerant piping is contained in AHU closet through floors state whether the refrigerant lines are in the closet walls through floors or through the floor in closet through the floor. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. i. R454B is a type A2 refrigerant. As per the 2018 IMC Section 1107.3 Pipe enclosures. ▪ Rigid or flexible metal enclosures or pipe ducts shall be provided for soft, annealed copper tubing and used for refrigerant piping erected on the premises and containing other than Group A1 or B1 refrigerants. Enclosures shall not be required for connections between condensing units and the nearest riser box(es), provided such connections do not exceed 6 feet (1829 mm) in length. ▪ Provide Detail of Refrigerant Chase. - 2018 IECC Section C103.2Information on construction documents. - 2018 IBC Section [A]107.2.1Information on construction documents. ▪ See Below State of Arizona adopted policy for Type A2 Refrigerants. ▪ Policy Title: Alternative Refrigerants Applicable Code Sections: International Mechanical Code Chapter 11 International Residential Code Chapter 14 Purpose: To establish a common set of regulations for the design and installation of cooling systems utilizing alternative refrigerants as mandated by the United States Environmental Protection Agency (EPA). Policy: Cooling systems may be designed and installed in accordance with the currently adopted International Mechanical Code (or International Residential Code as applicable) or the most current edition of ANSI/ASHRAE 15 with the companion standard ANSI/ASHRAE 34. Background: On October 24, 2023, the EPA published a final rule restricting the production and use of hydrofluorocarbon (HFC) refrigerants for residential and light commercial heating ventilation and air conditioning (HVAC) systems through the Technology Transitions Program. The rule, as originally issued, placed restrictions on both the manufacture and installation of HVAC products and systems beginning on January 1, 2025, utilizing HFC refrigerants. Alternative refrigerants that meet these new requirements are also new to the building and mechanical codes. While the newest building safety standards address how systems using these new refrigerants must be designed and installed, local authorities having jurisdiction (AHJ) may not have the new regulations adopted or implemented yet. For local AHJs to continue using their existing building safety codes, an option is needed for the refrigeration sections of those codes. Process: Permit applicants seeking to use alternative refrigerants that are not identified in the adopted building safety codes shall declare the use of ANSI/ASHRAE 15 with the companion standard ANSI/ASHRAE 34 for refrigerant system designs on permit application and/or the construction documents prior to submitting a permit application. Additional EPA Links: https://www.epa.gov/climate-hfcs-reduction/frequent-questions-phasedown-hydrofluorocarbons https://www.epa.gov/climate-hfcs-reduction/background-hfcs-and-aim-act https://www.epa.gov/climate-hfcs-reduction/technology-transitions City of Tucson Pima County Marana Oro Valley 520-790-5550 520-724-9000 520-382-2600 520-229-4800 Sierra Vista Sahuarita South Tucson 520-458-3315 520-822-8866 520-792-2424 |
||
02/11/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Perry Hendershott phendershott@safebuilt.com Denied Reason: Date Completed : 1/26/2025 10:39:35 PM Second Plumbing Review: Unresolved-1). Plan Page A1.5 & A1.6: Missing fixture spacing measurements for the double lavatories. Add fixture to sidewall & fixture distances for the double lavatories. -2018 IPC 405.3.1 Unresolved-2). Plan Page A2.4: Missing Adjacent secondary scupper locations. Add Adjacent secondary scupper locations.. -2018 IPC 1106.5, 1108 Unresolved-3). Plan Page D3.1: missing secondary scupper detail. Add secondary scupper detail. -2018 IPC 1106.5, 1108 |
||
02/12/2025 | Fire New Construction | REQUIRES RESUBMIT | -Could not locate your response to the original fire comments. Please provide a response regarding the fire alarm requirements as noted in the original comments. john.vincent@tucsonaz.gov 5203495581 |
||
02/05/2025 | Water - PDSD | REQUIRES RESUBMIT | Tucson Water does not offer a 2-1/2” water meter, see https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/tucson-water/documents/signed_meter_sizing_guidelines_march_2020.pdf for the available meter sizes and their maximum design capacities. Provide the size of the proposed reduced pressure backflow prevention (RPBP) assembly. Verify the actual pressure drops associated with the water meter and the RPBP. Note that according to Tucson Water, the minimum water pressure at that site is 75 PSI. [Initial comment: Provide the size of the water meter(s) serving this address, the size of the backflow preventer associated with the water meter(s), and the total water demand served by each water meter. Reference: Section 107.2.1, IBC 2018.] | ||
01/24/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |