Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - LIMITED v.3
Permit Number - TC-COM-1224-02357
Review Name: COMMERCIAL REVIEW - LIMITED v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/16/2025 | Commercial Building | APPROVED | |||
| 04/16/2025 | Commercial Electrical | APPROVED | |||
| 04/28/2025 | Commercial Plumbing | APPROVED | |||
| 04/28/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/28/2025 | Commercial Mechanical | REQUIRES RESUBMIT | 1. The COMcheck report shows that the proposed unit fails to meet the energy requirement. [Second comment: Comment not addressed. [Initial comment: Show that the proposed new rooftop unit meets the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.] 2. The COMcheck report shows that the proposed unit fails to meet the energy requirement. [Second comment: Comment not addressed. [Initial comment: Show that the new proposed heat pump meets the requirements of Section C403.5, IECC 2018 (economizer) unless exempted by compliance with the efficiency requirements of Table C403.5 (2) and Section C503.4.1, IECC 2018.] |
||
| 04/24/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 04/14/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |