Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/03/2025 Commercial Mechanical REQUIRES RESUBMIT 1. The A/C Equipment Heat Pump Schedule does not indicate that the unit, AC-1, includes the required economizer. Also, the factory information for the unit shows that the unit does not have an IEER rating. [Third comment: The COMcheck report shows that the proposed unit fails to meet the energy requirement.] [Second comment: Comment not addressed. [Initial comment: Show that the proposed new rooftop unit meets the requirements of Sections C403.3, C403.4, and C403.5 (e.g. provide the mechanical compliance certification from COMcheck). Reference: Section C501.4, International Energy Conservation Code 2018.]
2. The A/C Equipment Heat Pump Schedule does not indicate that the unit, AC-2, includes the required economizer. Also, the factory information for the unit shows that the unit does not have an IEER rating. [Third comment: The COMcheck report shows that the proposed unit fails to meet the energy requirement.] [Second comment: Comment not addressed. [Initial comment: Show that the new proposed heat pump meets the requirements of Section C403.5, IECC 2018 (economizer) unless exempted by compliance with the efficiency requirements of Table C403.5 (2) and Section C503.4.1, IECC 2018.]
3. Sign and date the COMcheck Mechanical Compliance Certificate.
05/27/2025 PDSD Application Completeness Express REVIEW COMPLETED