Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1224-02339
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 12/26/2024 | Commercial Building | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 12/23/2024 7:14:09 PM 1. Provide Special Inspections Intermediate Certificate ◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Provide signed/dated certificate: S0.1 states that special structural inspections shall be provided by the owner or owner’s representative. ◦ You may obtain the form at the following link: ◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf ◦ The Condition is added to the permit and then satisfied upon approval of the form. 2. Geotechnical investigations shall be conducted accordance with 2018 IBC section 1803.2 and reported in accordance with section 1803.6. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 12/23/2024 7:15:13 PM 1. A600 – EIFS wall doesn’t state the scope of special inspections required per 2018 IBC 1705.16. 2. T101 – Separate permits note 4 states engineered truss drawings are not within the scope but S1.2 roof framing plan shows pre-fab wood roof. (2018 IBC section 107.2.1) 3. T101 – List any deferred submittal components if any. S1.2 shows pre-fab canopies by others. Provide this manufacturer shop drawing/cut sheets. (2018 IBC section 107.2.1) 4. T103 – Code compliant summary missing applicable accessible code. Also “2009 International Life Safety Code” is not applicable to City of Tucson. List all applicable codes per City of Tucson. Lighting code is also missing. |
||
| 12/26/2024 | Commercial Electrical | REQUIRES RESUBMIT | Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 12/23/2024 7:14:57 PM 1. E001 – Key note 3 refer to civil drawings but civil drawings missing. (2018 IBC section 107.2.1) 2. E500 – Comments 6 refer to SL sheets for site lighting specifications but missing. Provide lumen calculation on plans (section 104.2.1), lighting area (section 301.1) and total outdoor light output (section 401.2) per 2012 City of Tucson/Pima County Outdoor Lighting Code. 3. E001 – Underground service feeders section detail missing. |
||
| 12/26/2024 | Commercial Mechanical | REQUIRES RESUBMIT | Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 12/23/2024 7:14:43 PM 1. M100 - Walk in cooler cut sheet missing. State if any deferred submittals. 2. A102/M100 – Keynote 13 weatherproof exterior penetration detail missing. Cooler manufacturer document missing. |
||
| 12/26/2024 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 12/23/2024 7:14:28 PM 1. P100 – Evaporators document missing. (2018 IPC section 106.3.1) 2. P100 – Keyed notes states to coordinate with Civil site utility plan but this is missing. |
||
| 01/08/2025 | Outdoor Lighting | REQUIRES RESUBMIT | Comments 6 refers to SL sheets for site lighting specifications but missing. Provide lumen calculation on plans (section 104.2.1), lighting area (section 301.1) and total outdoor light output (section 401.2) per 2012 City of Tucson/Pima County Outdoor Lighting Code. | ||
| 01/10/2025 | Site Engineering | REQUIRES RESUBMIT | 1. The associated development package TD-DEV-1024-00291 must be approved before this building permit can be approved. Mike Ortiz michael.ortiz@tucsonaz.gov |
||
| 01/13/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: PDSD Zoning Review Section PROJECT: TC-COM-1224-02339 - TD-DEV-1024-00291 3250 E SPEEDWAY BL. - C-3 Food Service (1st Review) TRANSMITTAL DATE: January 13, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-3 zone (UDC 4.7.22). Commercial Storage use is a permitted use in the zone (UDC Table 4.8-4). 1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-1024-00291 and although it appears that the building plan is in compliance until the DP is approved by all review agencies Zoning cannot approve this plan. If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov. |
||
| 01/09/2025 | Water - PDSD | REQUIRES RESUBMIT | 1. Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2018. 2. The applicable standard for a reduced pressure backflow prevention assembly is ASSE 1013 (see the Backflow Device Schedule, P400). |
||
| 01/07/2025 | Fire New Construction | REVIEW COMPLETED | |||
| 12/18/2024 | PDSD Application Completeness Express | REVIEW COMPLETED |