Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1224-02339
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/18/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/27/2025 | Commercial Building | REQUIRES RESUBMIT | Structural(S) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 2/27/2025 3:16:49 AM 1. Provide Special Inspections Intermediate Certificate ◦ A Special Inspections Intermediate Certificate must be submitted and reviewed prior to issuance of this permit. Provide signed/dated certificate: S0.1 states that special structural inspections shall be provided by the owner or owner’s representative. This was not resubmitted and still missing. ◦ You may obtain the form at the following link: ◦ https://www.tucsonaz.gov/files/sharedassets/public/v/1/city-services/planning-developmentservices/documents/special_inspection_certificate.pdf ◦ The Condition is added to the permit and then satisfied upon approval of the form. Building(B) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Approved with Comments Reason: Date Completed : 2/27/2025 3:19:05 AM |
||
| 02/27/2025 | Commercial Electrical | REQUIRES RESUBMIT | Electrical(E) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 2/27/2025 3:17:52 AM 1. E001 – Key note 3 refer to civil drawings but civil drawings missing. (2018 IBC section 107.2.1) Civil set still missing. 2. E500 – Comments 6 refer to SL sheets for site lighting specifications but missing. Provide lumen calculation on plans (section 104.2.1), lighting area (section 301.1) and total outdoor light output (section 401.2) per 2012 City of Tucson/Pima County Outdoor Lighting Code. Civil set missing from resubmission. |
||
| 02/27/2025 | Commercial Mechanical | REQUIRES RESUBMIT | Mechanical(M) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 2/27/2025 3:17:33 AM 1. M100 - Walk in cooler cut sheet missing. State if any deferred submittals. Still missing. |
||
| 02/27/2025 | Commercial Plumbing | REQUIRES RESUBMIT | Plumbing(P) Reviewer Kimiyoshi Shimabukuro kshimabukuro@safebuilt.com Denied Reason: Date Completed : 2/27/2025 3:17:14 AM 1. P100 – Evaporators document missing. (2018 IPC section 106.3.1) Still missing. 2. P100 – Keyed notes states to coordinate with Civil site utility plan but this is missing. C2.0 still missing (not on sheet index) |
||
| 03/04/2025 | Outdoor Lighting | REQUIRES RESUBMIT | Outdoor Lighting Review TC-COM-1224-02339 (3250 E SPEEDWAY BL TUCSON, AZ 85716) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Building Code (IBC), International Energy Conservation Code (IECC), 2017 National Electrical Code (NEC), 2012 Outdoor Lighting Code (OLC). https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/building-code/2012_outdoor_lighting_code_.pdf Outdoor Lighting Review: 1. Provide an outdoor lighting plan that meets the requirements of OLC 104.2. Show/locate the different light sources on your site plan. Number the light fixtures on your table and use the same number on your site plan 2. Show compliance with City of Tucson Outdoor Lighting Code with an approved lighting calculation in accordance with OLC 3.1.2. Include all exterior fixtures on the property in the calculations. Show unshielded fixtures with a maximum of 3,000 lumens, OLC 401.4. Show lamps with a maximum of 3500K color temperature, OLC 402.1. 3. Show compliance to total outdoor light output per 2012 City of Tucson/Pima County Outdoor Lighting Code section 401.2. Total outdoor light output shall not exceed the lumen limits listed in Table 401.1. 4. E1.1 – Lighting Code section 104.2.2. 4. Indicate whether or not a special inspection is required per sec. 104.2.2, and 106.2. 5. Specify any exceptions used. 6. Provide Curfew lighting controls If applicable Per section 403. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 03/18/2025 | Site Engineering | REQUIRES RESUBMIT | TC-COM-1224-02339 3250 E SPEEDWAY BL The building permit cannot be approved until the associated development package, TD-DEV-1024-00291, is approved. Per UDC Article 3.3.3.7.a The approved site plan (Development Package) on file with the PDSD is the basis for issuance of building permits. Chris Arrington chris.arrington@tucsonaz.gov |
||
| 03/05/2025 | Site Zoning | REQUIRES RESUBMIT | FROM: Ramiro Olivarez PDSD Zoning Review Section PROJECT: TC-COM-1224-02339 - TD-DEV-1024-00291 3250 E SPEEDWAY BL. - C-3 Food Service (2nd Review) TRANSMITTAL DATE: March 05, 2025 COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. This site is located in the C-3 zone (UDC 4.7.22). Commercial Storage use is a permitted use in the zone (UDC Table 4.8-4). 1. Zoning has reviewed the building permit for compliance with development package (DP) TD-DEV-1024-00291 and although it appears that the building plan is in compliance, until the DP is approved by all review agencies Zoning cannot approve this plan. If you have any questions about this transmittal, please contact Ramiro Olivarez at Ramiro.Olivarez@tucsonaz.gov |
||
| 03/11/2025 | Water - PDSD | REQUIRES RESUBMIT | Civil sheet C2.0 not included in submittal. Include C2.0 in the sheet index. [Initial comment: Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 107.2.1, IBC 2018.] | ||
| 02/25/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |