Permit Number: TC-COM-1223-02788
Parcel: 11206425B

Address:
2525 N TUCSON BL

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.2

Permit Number - TC-COM-1223-02788
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2025 Site Zoning Standard APPROVED
03/04/2025 Site Engineering Standard NOT REQUIRED
03/04/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
02/13/2025 Commercial Electrical REQUIRES RESUBMIT Permit Review TC-COM-1223-02788 (2525 N TUCSON BL TUCSON, AZ 85716)
2nd Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Building Code (IBC), 2017 National Electrical Code (NEC).


1. Add notations to the plans on the site map, and line diagrams, requiring that the Site-map-placard be placed at both the PV disconnect location and at the main service entrance.
2. Clarify the “Busbar Rating” and “Main Breaker Rating” as shown on the electrical schematic sheets. The line diagram shows the CT Meter Cabinet as rated at 1,200A, while the bus bar and main breaker ratings show 400A.
3. Specify interconnection method and note it on the plans. NEC 705.12
02/12/2025 Commercial Structural REQUIRES RESUBMIT Please submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed.
1. Provide structural design and calculations prepared and sealed by an Arizona licensed registrant, for the installation of the ballasted solar PV system to be mounted on the roof.
a. The requested engineering is to include, but not be limited to: Gravity and Uplift and Sliding resistance of the ballasted roof mount system. IBC Chapter 16.
b. Provide calculations and provide construction drawings to show how the PV system will resist the wind load and remain in place. Additionally provide a racking layout plan to show the ballast locations and number of blocks to be used in each.

Please feel free to call me to discuss further if necessary.

Mark Masek Plans Examiner Mark.masek@tucsonaz.gov 520-837-4994
02/20/2025 Fire New Construction Standard REVIEW COMPLETED Installation shall comply with Section 1204 of the 2024 IFC.
02/11/2025 PDSD Application Completeness Express REVIEW COMPLETED