Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.1
Permit Number - TC-COM-1222-00360
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
02/08/2023 | Commercial Plumbing | APPROVED | |||
02/08/2023 | Site Engineering | NOT REQUIRED | |||
02/17/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
02/17/2023 | Commercial Building | REQUIRES RESUBMIT | 1) Provide structural calculations supporting the proposed structural changes per page S1 including the new concrete footing and sizing of new headers. 2) Provide a written response to all review comments. Juan Garcia Juan.Garcia@tucsonaz.gov |
||
02/08/2023 | Commercial Electrical | REQUIRES RESUBMIT | The electric water heater FLA = 28.8 per the specs on the plumbing plans. Therefore 28.8 x 125% (per NEC continuous load) = 36 amps. Please revise the OCPD for the water heater to 40 amps and the feeder to #8 AWG Cu conductors. NEC 310.15(B)(16), 422.13. | ||
02/08/2023 | Commercial Mechanical | REQUIRES RESUBMIT | 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018. 2. Show that the specified heat pumps comply with the requirements of Section C403, IECC 2018. Reference: Section C502.2.3, IECC 2018. |
||
02/08/2023 | Site Zoning | REQUIRES RESUBMIT | FROM: Paul Camarena PDSD Zoning Review Section PROJECT: TC-COM-1222-00360 6400 E EL DORADO CI Zoning C-1 TRANSMITTAL DATE:ā€ˇFebruary 8, 2023 COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed. 1.COMMENT: Clarify the existing use. As it appears that you are proposing a change of use you will need to do one of the following: 1) Provide an approved C of O for a use that parks at a ratio of 1 space per 50 sq. ft. of gross floor area or more intense, 2) Demonstrate that the required vehicle parking for the bar use is provided on site, or 3) A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan. Additional comments may be forthcoming. If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov |
||
02/08/2023 | Fire New Construction | REVIEW COMPLETED | |||
02/04/2023 | PDSD Application Completeness | REVIEW COMPLETED |