Permit Number: TC-COM-1222-00360
Parcel: 13314459C

Review Status: Requires Resubmit

Review Details: COMMERCIAL REVIEW - FULL v.1

Permit Number - TC-COM-1222-00360
Review Name: COMMERCIAL REVIEW - FULL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
02/08/2023 Commercial Plumbing APPROVED
02/08/2023 Site Engineering NOT REQUIRED
02/17/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
02/17/2023 Commercial Building REQUIRES RESUBMIT 1) Provide structural calculations supporting the proposed structural changes per page S1 including the new concrete footing and sizing of new headers.
2) Provide a written response to all review comments.

Juan Garcia
Juan.Garcia@tucsonaz.gov
02/08/2023 Commercial Electrical REQUIRES RESUBMIT The electric water heater FLA = 28.8 per the specs on the plumbing plans. Therefore 28.8 x 125% (per NEC continuous load) = 36 amps. Please revise the OCPD for the water heater to 40 amps and the feeder to #8 AWG Cu conductors. NEC 310.15(B)(16), 422.13.
02/08/2023 Commercial Mechanical REQUIRES RESUBMIT 1. Provide heating and cooling load calculations to justify the heating/cooling capacities of the specified HVAC units. Reference: Section C403.1.1 and C502.2.3, IECC 2018.
2. Show that the specified heat pumps comply with the requirements of Section C403, IECC 2018. Reference: Section C502.2.3, IECC 2018.
02/08/2023 Site Zoning REQUIRES RESUBMIT FROM: Paul Camarena
PDSD Zoning Review Section

PROJECT: TC-COM-1222-00360
6400 E EL DORADO CI Zoning C-1

TRANSMITTAL DATE:ā€ˇFebruary 8, 2023


COMMENTS: Please resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

1.COMMENT: Clarify the existing use. As it appears that you are proposing a change of use you will need to do one of the following: 1) Provide an approved C of O for a use that parks at a ratio of 1 space per 50 sq. ft. of gross floor area or more intense, 2) Demonstrate that the required vehicle parking for the bar use is provided on site, or 3) A site plan (Development Package) is required for the following types of development: Existing development undergoing a change of use, building structure additions, and/or a reconfiguration of an area outside a building. A development package (DP) meeting the requirements of Administrative Manual (AM) 2-06 must be submitted and approved prior to approval of this building plan.

Additional comments may be forthcoming.





If you have any questions about this transmittal, Contact Paul Camarena at (520)837-4986 or by email Paul.Camarena@tucsonaz.gov
02/08/2023 Fire New Construction REVIEW COMPLETED
02/04/2023 PDSD Application Completeness REVIEW COMPLETED