Permit Number: TC-COM-1222-00254
Parcel: 11307046C

Review Status: Requires Resubmit

Review Details: BUILDING DEFERRED SUBMITTAL REVIEW v.2

Permit Number - TC-COM-1222-00254
Review Name: BUILDING DEFERRED SUBMITTAL REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/01/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/01/2024 External Reviewers - Stantec REQUIRES RESUBMIT March 29, 2024
1st Review

FORS architecture + interiors
Attn: John McColgin
2020 E. Broadway Blvd.
Tucson, Arizona 85719

Re: FIRST WATCH
REMODEL AND TENANT IMPROVEMENT (DEFERRED SUBMITTAL – TRUSSES)

City of Tucson Permit Number: TC-COM-1222-00254
Stantec Project Number: 185215066
Stantec File Number: TUC-24-030

Plan review for the above referenced project has been completed. This letter reflects comments to be addressed. To facilitate a shorter back-check time, we request that you please, only provide plans and calculation pages that have been revised, clouding any changes, along with a written response to each of the noted items indicating the action taken.

The scope of this review covers the architectural, structural, and mechanical designs as they relate to the codes adopted by the jurisdiction. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

Occupancy
Group Construction
Type Area
(Square feet) Occupant
Load Automatic
Fire Sprinklers Fire
Alarms
A-2 V-B 3,997 126 Yes Yes
Separate Permits: Automatic fire sprinklers, fire alarm, and kitchen hood suppression system.
Deferred Submittals: Prefabricated roof trusses and factory fabricated patio cover.
Special Inspections: Epoxy and expansion anchors, masonry, and outdoor lighting.

GENERAL COMMENTS

1. The submittal contains multiple pages upside down and sideways. Please re-submit all documents right-side up.

ARCHITECTURAL COMMENTS

General

1. The comments on the truss layout indicate that the architect and mechanical engineer must review the truss calculations for design compliance. The truss calculations do not include an approval by the architect and mechanical engineer though. Please have the registrants review and notate on the trusses that the deferred submittal is in conformance to the building design. [Ref. IBC 2018 Sec. 107.3.4.1]

STRUCTURAL COMMENTS

General

1. The submittal contains a typical roof opening design that appears to be fromm Schneider Structural Engineers. This design must be incorporated into the structural plans. Please include the design within the structural drawings and reference the detail on the roof framing plan.

2. The submittal includes 2 truss layouts both approved by the Schneider Structural Engineers. The second submittal includes some additional comments. Please remove the original approval from the set.

MECHANICAL COMMENTS

1. The mechanical cutsheet provided conflict the approved mechanical drawings dated 11/29/2023. The cut sheets do not include the Day & Night 6 ton unit. Please have the mechanical engineer review the units provided and update the mechanical plans accordingly.

PLUMBING COMMENTS

There are no comments.

ELECTRICAL COMMENTS

There are no comments.


Should you have any questions regarding the plan review comments, please contact the plan reviewer listed for the appropriate discipline.

Plans reviewed by:
Trevor Bies
Senior Plan Reviewer
602-338-9922
Trevor.bies@stantec.com
03/19/2024 PDSD Application Completeness Express REVIEW COMPLETED
03/25/2024 Special Inspection Certificate Review (Deferred Submittal) Express REVIEW COMPLETED EPOXY AND EXPANSION ANCHORS
03/25/2024 Special Inspection Certificate Review (Deferred Submittal) Express REVIEW COMPLETED POST INSTALLED ANCHORS
03/25/2024 Special Inspection Certificate Review (Deferred Submittal) Express REVIEW COMPLETED POST INSTALLED REBAR