07/13/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/13/2023 Commercial Electrical REQUIRES RESUBMIT Please address the following electrical plan review comments and provide a written response.

Only one electrical plan sheet ‘E-1’ was submitted. Could not locate notes that correlate with the encircles notes in the floor plan. Please clarify. IBC section 107.2.1.

The wording and numbers are not legible in the floor plan. IBC 107.2.1

The panel schedule identification of branch circuits assigned to devices is not specific enough to distinguish exact locations and suite associated with the devices. NEC 408.4.

Provide a lighting floor plan including lighting controls. Comply with 2018 IECC.

Provide a complete luminaire schedule.

Verify compliance with NEC 240.24(B). Each occupant shall have ready access to the overcurrent devices protecting conductors suppling that occupant.

Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC.