Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.3
Permit Number - TC-COM-1222-00233
Review Name: COMMERCIAL REVIEW - FULL v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/13/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/13/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please address the following electrical plan review comments and provide a written response. Only one electrical plan sheet ‘E-1’ was submitted. Could not locate notes that correlate with the encircles notes in the floor plan. Please clarify. IBC section 107.2.1. The wording and numbers are not legible in the floor plan. IBC 107.2.1 The panel schedule identification of branch circuits assigned to devices is not specific enough to distinguish exact locations and suite associated with the devices. NEC 408.4. Provide a lighting floor plan including lighting controls. Comply with 2018 IECC. Provide a complete luminaire schedule. Verify compliance with NEC 240.24(B). Each occupant shall have ready access to the overcurrent devices protecting conductors suppling that occupant. Ref; 2018 IBC section 107.2.1, 2017 NEC, 2018 IECC. |
||
| 06/12/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |