Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL REVIEW - FULL v.2
Permit Number - TC-COM-1222-00233
Review Name: COMMERCIAL REVIEW - FULL v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/08/2023 | Commercial Building | APPROVED | |||
| 01/24/2023 | Site Zoning | APPROVED | |||
| 01/30/2023 | Site Engineering | NOT REQUIRED | |||
| 02/08/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 02/08/2023 | Commercial Electrical | REQUIRES RESUBMIT | Please provide complete electrical and lighting plans showing all outlet and devices branch circuit/panel designations, and complete panel schedules including load calculations associated with the electrical devices, equipment, lighting utilized for this project. Provide a complete luminaire schedule. Provide compliance with the 2018 IECC for the lighting. Ref; 2018 IBC section 107.2.1, 2017 NEC art 408.4. 2018 IECC. |
||
| 01/24/2023 | Fire New Construction | REVIEW COMPLETED | |||
| 01/06/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |